Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 611 - PRIMARY DRINKING WATER STANDARDS
Subpart Z - ENHANCED TREATMENT FOR CRYPTOSPORIDIUM
Section 611.1015 - Requirements for Microbial Toolbox Components: Microbial Toolbox Options for Meeting Cryptosporidium Treatment Requirements
Universal Citation: 35 IL Admin Code ยง 611.1015
Current through Register Vol. 48, No. 38, September 20, 2024
a) Treatment Credits
1) A supplier receives the applicable of the
treatment credits set forth in subsection (b) by meeting the conditions for
microbial toolbox options described in Sections
611.1016 through
611.1020. The supplier applies
these treatment credits to meet the applicable treatment requirements set forth
in Section 611.1011 or Section
611.1012.
2) An unfiltered system supplier is eligible
for treatment credits for the microbial toolbox options described in Section
611.1020 only.
b) Subsections (b)(1) through (b)(5) summarize options in the microbial toolbox.
1) Source Protection and Management Toolbox
Options
A) Watershed Control Program.
0.5 -log credit for
Agency-approved program comprising required elements, annual program status
report to Agency, and regular watershed survey. An unfiltered system supplier
is not eligible for credit. Specific criteria are set forth in Section
611.1016(a).
B) Alternative source or intake management:
No prescribed credit. A supplier may conduct simultaneous monitoring for
treatment bin classification at alternative intake locations or under
alternative intake management strategies. Specific criteria are set forth in
Section 611.1016(b).
2) Pre-Filtration Toolbox Options
A) Presedimentation Basin with Coagulation.
0.5-log credit during any month that presedimentation basins achieve a monthly
mean reduction of 0.5-log or greater in turbidity or alternative
Agency-approved performance criteria. To be eligible, basins must be operated
continuously with coagulant addition and all plant flow must pass through
basins. Specific criteria are set forth in Section
611.1017(a).
B) Two-stage Lime Softening. 0.5-log credit
for two-stage softening if chemical addition and hardness precipitation occur
in both stages. All plant flow must pass through both stages. Single-stage
softening is credited as equivalent to conventional treatment. Specific
criteria are set forth in Section
611.1017(b).
C) Bank Filtration. 0.5-log credit for
25-foot setback or 1.0 -log credit for 50-foot
setback; the aquifer must be unconsolidated sand containing at least ten
percent fines and average turbidity in the wells must be less than 1 NTU. A
supplier using wells followed by filtration when conducting source water
monitoring must sample the well to determine bin classification and is not
eligible for additional credit. Specific criteria are set forth in Section
611.1017(c).
3) Treatment Performance Toolbox
Options
A) Combined Filter Performance.
0.5-log credit for combined filter effluent turbidity less than or equal to
0.15 NTU in at least 95 percent
of measurements each month. Specific criteria are set forth in Section
611.1018(a).
B) Individual Filter Performance. 0.5-log
credit (in addition to 0.5-log combined filter performance credit) if
individual filter effluent turbidity is less than or equal to
0.15 NTU in at least 95 percent
of samples each month in each filter and is never greater than
0.3 NTU in two consecutive
measurements in any filter. Specific criteria are set forth in Section
611.1018(b).
C) Demonstration of Performance. Credit
awarded to unit process or treatment train based on a demonstration to the
Agency with an Agency-approved protocol. Specific criteria are set forth in
Section 611.1018(c).
4) Additional Filtration Toolbox
Options
A) Bag or Cartridge Filters
(individual filters). Up to 2-log credit based on the removal efficiency
demonstrated during challenge testing with a 1.0-log factor of safety. Specific
criteria are set forth in Section
611.1019(a).
B) Bag or Cartridge Filters (in series). Up
to 2.5 -log credit based on the
removal efficiency demonstrated during challenge testing with a 0.5-log factor
of safety. Specific criteria are set forth in Section
611.1019(a).
C) Membrane Filtration. Log credit equivalent
to removal efficiency demonstrated in challenge test for device if supported by
direct integrity testing. Specific criteria are set forth in Section
611.1019(b).
D) Second Stage Filtration. 0.5-log credit
for second separate granular media filtration stage if treatment train includes
coagulation prior to first filter. Specific criteria are set forth in Section
611.1019(c).
E) Slow Sand Filters. 2.5-log credit as a
secondary filtration step or
3.0 -log credit as a primary
filtration process. No prior chlorination for either option. Specific criteria
are set forth in Section
611.1019(d).
5) Inactivation Toolbox Options
A) Chlorine Dioxide. Log credit based on
measured CT in relation to CT table. Specific criteria are set forth in Section
611.1020(b).
B) Ozone. Log credit based on measured CT in
relation to CT table. Specific criteria are set forth in Section
611.1020(b).
C) UV. Log credit based on validated UV dose
in relation to UV dose table; reactor validation testing required to establish
UV dose and associated operating conditions. Specific criteria are set forth in
Section 611.1020(d).
BOARD NOTE: This Section derives from 40 CFR 141.715.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.