Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 611 - PRIMARY DRINKING WATER STANDARDS
Subpart I - DISINFECTANT RESIDUALS, DISINFECTION BYPRODUCTS, AND DISINFECTION BYPRODUCT PRECURSORS
Section 611.385 - Treatment Technique for Control of Disinfection Byproduct (DBP) Precursors
Current through Register Vol. 48, No. 38, September 20, 2024
a) Applicability
b) Enhanced Coagulation and Enhanced Softening Performance Requirements
Step 1 Required Removal of TOC by Enhanced Coagulation and Enhanced Softening for a Subpart B System Supplier Using Conventional
Treatment1,2 |
|||
Source-water TOC, mg/l |
Source-water alkalinity, mg/l as CaCO3 |
||
0-60 |
> 60-120 |
> 1203 |
|
> 2.0-4.0 |
35.0 % |
25.0 % |
15.0 % |
> 4.0-8.0 |
45.0 % |
35.0% |
25.0% |
> 8.0 |
50.0 % |
40.0 % |
30.0 % |
1 A supplier meeting at least one of the conditions in subsections (a)(2)(A) through (a)(2)(F) are not required to operate with enhanced coagulation. |
|||
2 A softening system that meets one of the alternative compliance standards in subsection (a)(3)is not required to operate with enhanced softening. |
|||
3 A supplier that practices softening must meet the TOC removal requirements in this column. |
Enhanced Coagulation Step 2 Target pH |
|
Alkalinity (mg/l as CaCO3) |
Target pH |
0-60 |
5.5 |
> 60-120 |
6.3 |
> 120-240 |
7.0 |
> 240 |
7.5 |
c) Compliance Calculations
d) Treatment Technique Requirements for Disinfection Byproduct (DBP) Precursors. Treatment techniques to control the level of disinfection byproduct (DBP) precursors in drinking water treatment and distribution systems, for a Subpart B system supplier using conventional treatment, are enhanced coagulation or enhanced softening.
BOARD NOTE: Derived from 40 CFR 141.135.