Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 604 - DESIGN, OPERATION, AND MAINTENANCE CRITERIA
Subpart O - CROSS CONNECTIONS
Section 604.1515 - Agency Approved Cross Connection Control Measures
Current through Register Vol. 48, No. 38, September 20, 2024
a) For all mains, pipes, structures through which water is obtained and distributed to the public, including wells and well structures, intakes and cribs, pumping stations, treatment plants, reservoirs, storage tanks and appurtenances, collectively or severally, actually used or intended for use for the purpose of furnishing water for drinking or domestic use, cross connection devises must be used as set forth in this Section.
b) Except as provided in this Section, a fixed air gap must be used.
c) Atmospheric vacuum breakers may be installed subject to the following conditions:
d) Examples of acceptable installations of atmospheric vacuum breakers include:
e) Reduced pressure principle backflow preventers may be installed subject to the following conditions: