Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 604 - DESIGN, OPERATION, AND MAINTENANCE CRITERIA
Subpart N - DISTRIBUTION
Section 604.1410 - Materials
Universal Citation: 35 IL Admin Code ยง 604.1410
Current through Register Vol. 48, No. 38, September 20, 2024
a) All materials, including ductile iron pipe, steel pipe, concrete pipe, plastic pipe, pipe liners, joints, fittings, valves and fire hydrants, must conform to the AWWA, ASTM, ANSI or NSF standards incorporated by reference at 35 Ill. Adm. Code 601.115.
b) Plastic Pipe
1) Plastic Pipe Specifications. Polyvinyl
Chloride (PVC), Chlorinated Polyvinyl Chloride (CPVC), Molecularly Oriented
Polyvinyl Chloride (PVCO) and Polyethylene (PE) must conform to NSF Standard
14, incorporated by reference in 35 Ill. Adm. Code 601.115.
2) PVC, CPVC, PVCO and PE pipe may be used
for water mains in accordance with this Section.
A) PVC may be used for water mains in
accordance with the following standards, incorporated by reference in 35 Ill.
Adm. Code 601.115:
i) AWWA C900-07;
ii) ASTM D 1784-11;
iii) ASTM D 1785-15;
iv) ASTM D 2241-09.
B) PE pipe may be used for water mains in
accordance with AWWA C906, incorporated by reference in 35 Ill. Adm. Code
601.115.
C) PVCO pipe may be used
for water mains in accordance with AWWA C909, incorporated by reference in 35
Ill. Adm. Code 601.115.
D) CPVC
pipe may be used for water mains in accordance with the following standards,
incorporated by reference in 35 Ill. Adm. Code 601.115:
i) ASTM F 441/F 441M;
ii) ASTM F 442/F 442M;
iii) ASTM D 1784.
3) Jointing
A) Jointing must be pressure slip jointed,
solvent welded, heat welded, flange or threaded joint.
B) Clean, dry contact surfaces are required
when making solvent or heat welded joints. Adequate setting time must be
allowed for maximum strength.
C)
Elastomeric seals (gaskets) used for push-on joints must comply with ASTM F 477
and must be pressure rated in accordance with ASTM D 3139.
D) Solvent cement must be specific for the
piping material and must comply with ASTM D 2564 for PVC and ASTM F 493 for
CPVC and must comply with Section 604.105(f).
4) Plastic Pipe Fittings
A) PVC fabricated fittings, 4-inch through
60-inch, must conform to AWWA C900.
B) Polyethylene pressure pipe fitting, 4-inch
through 63-inch, must conform to AWWA C906.
C) Injection-molded PVC pressure fittings,
4-inch through 12-inch, must conform to AWWA C907.
D) Schedule 40 or 80 PVC and CPVC pipe
fittings must be of the same material as the pipe and must comply with ASTM
Standards as follows:
i) ASTM D 2466 for PVC
Schedule 40;
ii) ASTM D 2467 for
PVC Schedule 80;
iii) ASTM D 2464
for threaded Schedule 80;
iv) ASTM
F 438 for Socket-Type CPVC Schedule 40;
v) ASTM F 439 for CPVC Schedule 80;
and
vi) ASTM F 437 for threaded
CPVC Schedule 80.
E)
Plastic fitting material must conform to ANSI/NSF Standard 14 and comply with
Section 604.105(f).
F) All fittings
must bear the NSF seal of approval.
c) Protection from Organic Compounds
1) When distribution systems are installed in
areas contaminated by organic compounds:
A)
pipe and joint materials must be protected; and
B) protection must extend at least 25 feet
laterally from the areas contaminated by organic compounds.
2) Where distribution systems are
installed within 25 feet of potential sources of organic compound
contamination, including any unit at a facility or a site that stores or
accumulates petroleum at any time above ground or below ground, pipe and joint
materials must be protected from organic compounds.
3) Protection from organic compounds may
include the following:
A) use of ductile iron
pipe with a Viton® or nitrile gasket, unless
otherwise approved by the Agency under Section 604.145(b);
B) remediation;
C) use of steel pipe;
D) encasement of the pipe; and
E) secondary containment of the
source.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.