Section 604.1310 - Access to Water Storage Structures
Universal Citation: 35 IL Admin Code ยง 604.1310
Current through Register Vol. 48, No. 38, September 20, 2024
a) Finished water storage structures must be designed with access to the interior for cleaning and maintenance.
b) At least two manholes must be provided above the waterline at each water compartment where space permits.
c) For elevated storage structures:
1) at least one of the access manholes must
be framed at least four inches above the surface of the roof at the opening,
must be fitted with a solid watertight cover that overlaps the framed opening
and extends down around the frame at least two inches, must be hinged on one
side, and must have a locking device; and
2) all other manholes or access ways not
conforming to subsection (c)(1) must be bolted and gasketed so that they are
watertight.
d) For ground level structures or flat roof structures:
1) each manhole must be elevated at least 24
inches above the top of the tank or covering sod, whichever is
higher;
2) each manhole must be
fitted with a solid watertight cover that overlaps a framed opening and extends
down around the frame at least two inches;
3) the frame must be at least four inches
high; and
4) each cover must be
hinged on one side, and must have a locking device.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.