a) Storage facilities must have sufficient capacity to meet domestic demands and, where fire protection is provided, fire flow demands.
b) Excessive storage capacity must be avoided to prevent potential water quality deterioration problems and freezing.
c) The material used in the construction of water storage structures must be approved by the Agency under 35 Ill. Adm. Code 602.105. Porous materials, including wood and concrete block, are not acceptable.
d) Storage Structure Drainage
e) The bottom of a water storage structure must be placed above the groundwater table, preferably above grade. At least 50 percent of the water depth must be above grade.
f) Finished water storage must be designed to facilitate turnover of water to avoid stagnation.
g) Freezing
h) The discharge pipes from water storage structures must be located to prevent the flow of sediment into the distribution system.
i) The area surrounding a ground level structure must be graded to prevent surface water from standing within 50 feet.
j) Minimum distances from sources of contamination for below ground storage reservoirs must be maintained as specified in Section 604.150(a).
k) A smooth-nosed sampling tap must be provided to facilitate collection of water samples for both bacteriological and chemical analyses.