Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 604 - DESIGN, OPERATION, AND MAINTENANCE CRITERIA
Subpart J - OTHER TREATMENT
Section 604.1010 - Iron and Manganese Control
Universal Citation: 35 IL Admin Code ยง 604.1010
Current through Register Vol. 48, No. 38, September 20, 2024
a) Except as provided in 35 Ill. Adm. Code 611.300(e), treatment is required to meet the iron and manganese MCL as stated in Section 611.300(b).
b) Removal of Iron and Manganese by Oxidation, Detention, and Filtration
1)
Oxidation must be by aeration, as indicated in Subpart D, unless the community
water supply demonstrates chemical oxidation provides equivalent results to
aeration. Chemicals that may be used for oxidation include chlorine, sodium
permanganate, potassium permanganate, ozone, or chlorine dioxide.
2) Detention
A) A minimum detention time of 30 minutes
must be provided following aeration to ensure that the oxidation reactions are
complete prior to filtration. This minimum detention time may be modified only
when a pilot plant study indicates completion of oxidation reactions in less
time.
B) The reaction
tank/detention basin must be provided with an overflow, vents, and access
hatches in accordance with Subpart M.
3) Filtration. Filters must conform to
Subpart F.
c) Removal by Manganese Greensand or Manganese Coated Media Filtration
1) Permanganate or chlorine must be added to
the water upstream of the filter, per the manufacturer's
recommendation.
2) An anthracite
media cap of at least six inches must be provided over manganese
greensand.
3) Normal backwash rate
is 8 gal/min/ft2 with filters containing manganese
greensand and 15 gal/min with manganese coated media.
4) Sample taps must be provided:
A) prior to application of
permanganate;
B) immediately ahead
of filtration;
C) at points between
the anthracite media and the manganese greensand;
D) halfway down the manganese greensand;
and
E) at the filter
effluent.
d) Sequestration of Iron or Manganese by Polyphosphates
1) Sequestration by polyphosphates must not
be used when the combination of iron and manganese exceeds 1 mg/L.
2) Phosphate solution must be kept covered
and disinfected by carrying approximately 10 mg/L free chlorine residual unless
the phosphate is not able to support bacterial growth and the phosphate is
being fed from the covered shipping container. Phosphate solutions having a pH
of 2.0 or less may also be exempted
from this requirement by the Agency.
3) Polyphosphates must not be applied ahead
of iron and manganese removal treatment. The point of application must be prior
to aeration, oxidation, or disinfection.
4) The phosphate feed point must be located
as far ahead of the oxidant feed point as possible.
e) Sequestration of Iron or Manganese by Sodium Silicates:
1) Sequestration by sodium
silicate must not be used when iron, manganese, or a combination of iron and
manganese exceeds 2 mg/L.
2) A
full-scale demonstration will be required to determine the suitability of
sodium silicate for the particular water and the minimum feed needed.
3) Chlorine or chlorine dioxide addition must
accompany the sodium silicate addition.
4) Sodium silicate must not be applied ahead
of iron or manganese removal treatment.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.