Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 604 - DESIGN, OPERATION, AND MAINTENANCE CRITERIA
Subpart D - AERATION
Section 604.410 - Spray Aeration
Universal Citation: 35 IL Admin Code ยง 604.410
Current through Register Vol. 48, No. 38, September 20, 2024
Spray aeration design must provide:
a) a hydraulic head of between 5 and 25 feet;
b) nozzles, with the size, number, and spacing of the nozzles being dependent on the flow rate, the space, and amount of head available;
c) nozzle diameters in the range of 1 to 1.5 inches to minimize clogging; and
d) an enclosed basin to contain the spray, with any openings protected by a 24-mesh screen.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.