Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 604 - DESIGN, OPERATION, AND MAINTENANCE CRITERIA
Subpart B - SOURCE DEVELOPMENT
Section 604.235 - Groundwater Quality
Current through Register Vol. 48, No. 38, September 20, 2024
a) Each community water supply using groundwater must collect and analyze one sample per well per month for total coliform bacteria. The analysis must be performed by a certified laboratory.
b) The Agency must require multiple barrier treatment to achieve at least 99.99 percent (4-log) removal or inactivation of viruses for all groundwater sources subject to bacteriological contamination.
c) When maintenance or equipment replacement on a well occurs that does not require a construction or operating permit under 35 Ill. Adm. Code 602, one sample from the well must be submitted to a certified laboratory for analysis for total coliform bacteria.
d) A source water assessment under Section 604.315 must be completed considering factors, both natural and manmade, that may affect water quality in the groundwater.