Section 370.1130 - Low Rate Intermittent or Periodically Dosed Sand Filters
Current through Register Vol. 48, No. 38, September 20, 2024
a) Applicability
b) Design Criteria
The criteria of Section 370.940(b), (c), and (f)(3), are generally applicable to intermittent sand filters used as tertiary filtration units.
The dosing facilities shall be sized to provide for a 12-hour dosing cycle for each bed.
Siphons (at minimum head) or pumps shall have a discharge capacity at least 100 percent in excess of the maximum rate of inflow to the dosing tank, including recirculation, and at average head, at least 90 gallons per minute per 1,000 square feet being dosed.
Provision for recirculation of filter effluent may be included to improve process flexibility.
A recirculation rate of up to 100% of design average flow to the filter may be provided.
Capability for varying the recirculation rate shall be provided.
The hydraulic load of secondary wastewater applied to supplemental intermittent sand filters shall not exceed 15 gallons per day (gpd)/sq. ft. More conservative application rates should be provided for low quality filter influents. Refer to subsection (d)(3) below.
c) Construction Details
The criteria of Section 370.940(g) are generally applicable to tertiary intermittent sand filters. Also, refer to subsection (d).
d) Special Design Considerations in Lagoon Systems
Low rate sand filter systems that are intermittently or periodically dosed may be used to reduce suspended solids from multicell aerated or nonaerated sewage lagoon treatment plants.
Lagoons which have sand filters shall be designed to provide storage of flows received during cold weather when the filter is expected to be inoperable.
The design should include allowance for periodic dosing of varied volumes onto the filter while the filter discharge is shut off, then to be followed by a filtration period to completely empty the filter at a controlled rate.
The filter shall be designed for flexibility of dosing depth from 6 inches to 2 feet.
The dosing inlet structures shall be designed to dissipate inlet velocity and prevent sand scouring during the dosing period at the high dose rates. The inlet structures should be arranged to not interfere with maintenance of the sand surface.
The filter containment may be of vertical concrete walls on three sides (refer to subsection (d)(6) below) or sloped earthen berms with impervious lining, constructed to insure that no ground surface runoff or silts get onto the sand surface. A freeboard of 1 foot above the maximum design dosing depth should be provided.
The filter should be designed with a ramp on one end sloped and surfaced for access to the edge of the bed by wheeled vehicle to facilitate removing and replacement of sand. For larger filters, concrete tracks at the level of the sand surface may be desirable to reduce distance sand must be handled.