Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 229 - HOSPITAL/MEDICAL/INFECTIOUS WASTE INCINERATORS
Subpart L - RECORDKEEPING AND REPORTING REQUIREMENTS
Appendix B - Operating Parameters to be Monitored and Minimum Measurement and Recording Frequencies
An "X" in any box in this matrix means that measurement of that parameter is required.
MINIMUM FREQUENCY |
CONTROL SYSTEM |
||||||
Operating Parameters |
Data Measurement |
Data Recording |
Dry Scrubber Followed by Fabric Filter |
Wet Scrubber |
Dry Scrubber Followed by Fabric Filter and Wet Scrubber |
Selective Noncatalytic Reduction System |
|
Maximum Charge Rate1 |
Continuous |
Once per hour |
X |
X |
X |
X |
|
Maximum Fabric Filter Inlet Temperature |
Continuous |
Once per minute |
X |
X |
|||
Maximum Flue Gas Temperature |
Continuous |
Once per minute |
X |
X |
|||
Minimum Secondary Chamber Temperature |
Continuous |
Once per minute |
X |
X |
X |
X |
|
Minimum Dioxin/Furan Sorbent Flow Rate |
Hourly |
Once per hour |
X |
X |
|||
Minimum HCl Sorbent Flow Rate |
Hourly |
Once per hour |
X |
X |
|||
Minimum Reagent Flow Rate |
Hourly |
Once per hour |
X |
||||
Minimum Hg Sorbent Flow Rate |
Hourly |
Once per hour |
X |
X |
|||
Minimum Pressure Drop Across the Wet Scrubber or Minimum Horsepower or Amperage to Wet Scrubber |
Continuous |
Once per minute |
X |
X |
|||
Minimum Scrubber Liquor Flow Rate |
Continuous |
Once per hour |
X |
X |
|||
Minimum Scrubber Liquor pH |
Continuous |
Once per hour |
X |
X |
1For batch HMIWIs, record the charge per batch.