Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 229 - HOSPITAL/MEDICAL/INFECTIOUS WASTE INCINERATORS
Subpart H - COMPLIANCE REQUIREMENTS
Section 229.160 - Compliance Requirements for Rural HMIWIs

Current through Register Vol. 48, No. 38, September 20, 2024

a) Prior to January 1, 2014, the requirements set forth in subsections (c) through (e) of this Section shall apply to all rural HMIWIs subject to the emissions limits under Section 229.126 of this Part.

b) On and after January 1, 2014, the requirements set forth in subsections (c) through (e) of this Section shall apply to all rural HMIWIs that are not equipped with an air pollution control device and that are subject to the emissions limits under Section 229.126 of this Part.

c) Following the date on which the initial performance test is completed or is required to be completed under Section 229.142 of this Subpart, whichever date comes first, the owners or operators of rural HMIWI shall not operate their HMIWI either above the maximum charge rate or below the minimum secondary chamber temperature measured as 3-hour rolling averages (calculated each hour as the average of the previous 3 operating hours) at all times.

d) Operating parameter limits do not apply during performance tests.

e) Except as provided in Section 229.164 of this Subpart, the simultaneous operation of a rural HMIWI above the maximum charge rate and below the minimum secondary chamber temperature (calculated as a 3-hour rolling average) shall constitute a violation of the PM, CO and dioxin/furan emission limits.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.