a) No person shall cause or allow the transfer of gasoline into any delivery vessel from any bulk gasoline terminal unless:
1) The
bulk gasoline terminal is equipped with a vapor control system that limits
emission of VOM to 80 mg/1 (0.00067 lbs/gal) of gasoline loaded;
2) The vapor control system is operating and
all vapors displaced in the loading of gasoline to the delivery vessel are
vented only to the vapor control system;
3) There is no liquid drainage from the
loading device when it is not in use;
4) All loading and vapor return lines are
equipped with fittings which are vapor tight; and
5) The delivery vessel displays the
appropriate sticker pursuant to the requirements of Section
219.584(b) or (d)
of this Part; or, if the terminal is
driver-loaded, the terminal owner or operator shall be deemed to be in
compliance with this Section when terminal access authorization is limited to
those owners and/or operators of delivery vessels who have provided a current
certification as required by Section
219.584(c)(3)
of this Part.
b) The operator of a bulk gasoline terminal shall:
1)
Operate the terminal vapor collection system and gasoline loading equipment in
a manner that prevents:
A) Gauge pressure from
exceeding 18 inches of water and vacuum from exceeding 6 inches of water as
measured as close as possible to the vapor hose connection; and
B) A reading equal to or greater than 100
percent of the lower explosive limit (LEL measured as propane) when tested in
accordance with the procedure described in EPA 450/2-78-051 Appendix B,
incorporated by reference in Section
219.112
of this Part; and
C) Avoidable
leaks of liquid during loading or unloading operations.
2) Provide a pressure tap or equivalent on
the terminal vapor collection system in order to allow the determination of
compliance with Section
219.582(d)(1)(A)
of this Part; and
3) Within 15
business days after discovery of the leak by the owner, operator, or the Agency
repair and retest a vapor collection system which exceeds the limits of
subsection (c)(1)(A) or (B) of this Section.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.