Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 217 - NITROGEN OXIDES EMISSIONS
Subpart M - ELECTRICAL GENERATING UNITS
Section 217.344 - Emissions Limitations

Current through Register Vol. 48, No. 38, September 20, 2024

On and after January 1, 2015, no person shall cause or allow emissions of NOx into the atmosphere from any fossil fuel-fired stationary boiler to exceed the following limitations. Compliance must be demonstrated with the applicable emissions limitation on an ozone season and annual basis.

Fuel

Emission Unit Type

Nox Emissions Limitation (lb/mmBtu)

Solid

Boiler

0.12

Natural gas

Boiler

0.06

Liquid

Boiler that commenced operation before January 1, 2008

0.10

Boiler that commenced operation on or after January 1, 2008

0.08

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.