a) Except as provided for under Section 217.152, on and after January 1, 2015, no person shall cause or allow emissions of NOx into the atmosphere from any industrial boiler to exceed the following limitations. Compliance must be demonstrated with the applicable emissions limitation on an ozone season and annual basis.

Fuel

Emission Unit Type and Rated Heat Input Capacity (mmBtu/hr)

Nox Emissions Limitation (lb/mmBtu) or Requirement

Natural Gas or Other Gaseous Fuels

Industrial boiler greater than 100

0.08

Industrial boiler less than or equal to 100

Combustion tuning

Distillate Fuel Oil

Industrial boiler greater than 100

0.10

Industrial boiler less than or equal to 100

Combustion tuning

Other Liquid Fuels

Industrial boiler greater than 100

0.15

Industrial boiler less than or equal to 100

Combustion tuning

Solid Fuel

Industrial boiler greater than 100, circulating fluidized bed combustor

0.12

Industrial boiler greater than 250

0.18

Industrial boiler greater than 100 but less than or equal to 250

0.25

Industrial boiler less than or equal to 100

Combustion tuning

b) For an industrial boiler combusting a combination of natural gas, coke oven gas, and blast furnace gas, the NOx emissions limitation shall be calculated using the following equation:

NOx emissions limitation for period in lb/mmBtu

=

Image

Where:

Image

=

0.084 lb/mmBtu for natural gas

Image

=

the heat inpu of natural gas in Btu over that period

Image

=

0.144 lb/mmBtu for coke oven gas

Image

=

the heat input of coke oven gas in Btu over that period

Image

=

0.0288 lb/mmBtu for blast furnace gas

Image

=

the heat input of blast furnace gas in Btu over that period

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.