a)
Except as provided in subsections (b), (c), and (d), on and after January 1,
2017, the owner or operator of a process emission source must comply with the
following:
1) The sulfur content of all
residual fuel oil used by the process emission source must not exceed 1000
ppm;
2) The sulfur content of all
distillate fuel oil used by the process emission source must not exceed 15 ppm;
and
3) The owner or operator must:
A) Maintain records demonstrating that the
fuel oil used by the process emission source complies with the requirements in
subsections (a)(1) and (a)(2), such as records from the fuel supplier
indicating the sulfur content of the fuel oil;
B) Retain the records for at least 5 years,
and provide copies of the records to the Agency within 30 days after receipt of
a request by the Agency; and
C)
Notify the Agency within 30 days after discovery of deviations from any of the
requirements in this subsection (a). At minimum, and in addition to any
permitting obligations, such notification must include a description of the
deviations, a discussion of the possible cause of the deviations, any
corrective actions taken, and any preventative measures taken.
b) The sulfur content
limitation for distillate fuel oil in subsection (a)(2) does not apply to
distillate fuel oil used by "TC-F/TC-L/TCL Wing 5" and "TC-F/TC-L Alternative"
at Caterpillar Technical Center (located at or near 1311 E. Cedar Hills Dr.,
Mossville IL) for purposes of research and development or testing of equipment
intended for sale outside of Illinois. This exemption is limited to a combined
total of 150,000 gallons of distillate fuel oil per calendar year. The sulfur
content of the fuel oil must not exceed 500 ppm. The owner or operator of the
process emission sources described in this subsection must also comply with the
following:
1) Maintain records indicating the
amount of distillate fuel oil used by the process emission sources each
calendar year for purposes of research and development or testing of equipment
for sale outside of Illinois, as well as records demonstrating that the fuel
oil complies with the requirements in this subsection (b), such as records from
the fuel supplier indicating the sulfur content of the fuel oil;
2) Retain the records for at least 5 years,
and provide copies of the records to the Agency within 30 days after receipt of
a request by the Agency; and
3)
Notify the Agency within 30 days after discovery of deviations from any of the
requirements in this subsection (b). At minimum, and in addition to any
permitting obligations, the notification must include a description of the
deviations, a discussion of the possible cause of the deviations, any
corrective actions taken, and any preventative measures taken.
c) The sulfur content limitation
for distillate fuel oil in subsection (a)(2) does not apply to existing process
emission sources at Caterpillar's Montgomery facility (located at or near 325
South Route 31, Montgomery IL). The owner or operator of these process emission
sources must instead comply with the following:
1) On and after January 1, 2016:
A) The sulfur content of all distillate fuel
oil purchased for use by the process emission sources must not exceed 15 ppm;
and
B) The sulfur content of all
distillate fuel oil used by the process emission sources must not exceed 500
ppm;
2) The owner or
operator must:
A) Maintain records
demonstrating that the distillate fuel oil purchased on and after January 1,
2016, for use by the process emission sources, complies with the requirements
in subsection (c)(1)(A), such as records from the fuel supplier indicating the
sulfur content of the fuel oil, and maintain records indicating the date of
purchase of the fuel oil;
B)
Maintain records demonstrating that the distillate fuel oil used on and after
January 1, 2016, by the process emission sources, complies with the
requirements in subsection (c)(1)(B), such as records from the fuel supplier
indicating the sulfur content of the fuel oil;
C) Retain all records required by this
subsection (c) for at least 5 years, and provide copies of the records to the
Agency within 30 days after receipt of a request by the Agency; and
D) Notify the Agency within 30 days after
discovery of deviations from any of the requirements in this subsection (c). At
minimum, and in addition to any permitting obligations, the notification must
include a description of the deviations, a discussion of the possible cause of
the deviations, any corrective actions taken, and any preventative measures
taken.
d) The
sulfur content limitation for distillate fuel oil in subsection (a)(2) does not
apply to existing electric generating units at Midwest Generation's Fisk
station (located at or near 1111 W. Cermak Road, Chicago IL) or Waukegan
station (located at or near 401 E. Greenwood Avenue, Waukegan IL). The owner or
operator of these electric generating units must instead comply with the
following:
1) From January 1, 2016 through
December 31, 2018, the sulfur content of all distillate fuel oil purchased for
use by these electric generating units must not exceed 15 ppm;
2) From January 1, 2017 through December 31,
2018, the sulfur content of all distillate fuel oil used by these electric
generating units must not exceed 500 ppm;
3) On and after January 1, 2019, the sulfur
content of all distillate fuel oil used by these electric generating units must
not exceed 15 ppm;
4) The owner or
operator must:
A) Maintain records
demonstrating that the distillate fuel oil purchased from January 1, 2016
through December 31, 2018, for use by the electric generating units, complies
with the requirements in subsection (d)(1), such as records from the fuel
supplier indicating the sulfur content of the fuel oil, and maintain records
indicating the date of purchase of the fuel oil;
B) Maintain records demonstrating that the
distillate fuel oil used from January 1, 2017 through December 31, 2018, by the
electric generating units, complies with the requirements in subsection (d)(2),
such as records from the fuel supplier indicating the sulfur content of the
fuel oil;
C) On and after January
1, 2019, maintain records demonstrating that the distillate fuel oil used by
the electric generating units complies with the requirements in subsection
(d)(3), such as records from the fuel supplier indicating the sulfur content of
the fuel oil;
D) Retain all records
required by this subsection (d) for at least 5 years, and provide copies of the
records to the Agency within 30 days after receipt of a request by the Agency;
and
E) Notify the Agency within 30
days after discovery of deviations from any of the requirements in this
subsection (d). At minimum, and in addition to any permitting obligations, the
notification must include a description of the deviations, a discussion of the
possible cause of the deviations, any corrective actions taken, and any
preventative measures taken.