Illinois Administrative Code
Title 32 - ENERGY
Part 340 - STANDARDS FOR PROTECTION AGAINST RADIATION
Subpart H - RESPIRATORY PROTECTION AND CONTROLS TO RESTRICT INTERNAL EXPOSURE IN RESTRICTED AREAS
Section 340.710 - Use of Process or Other Engineering Controls
Universal Citation: 32 IL Admin Code ยง 340.710
Current through Register Vol. 48, No. 38, September 20, 2024
a) The licensee shall use, to the extent practicable, process or other engineering controls (e.g., containment or ventilation) to control the concentrations of radioactive material in air.
b) The licensee shall measure airflow rates initially and semiannually thereafter to assure proper ventilation system performance. Records of the evaluation of ventilation system performance shall be maintained for Agency inspection and shall include:
1) The date of evaluation;
2) Results of ventilation rate
measurements;
3) Manufacturer,
model and serial number of the measurement instrument used; and
4) The identity of the individual performing
the measurements.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.