Idaho Administrative Code
Title IDAPA 58 - Environmental Quality, Department of
Rule 58.01.08 - IDAHO RULES FOR PUBLIC DRINKING WATER SYSTEMS
Section 58.01.08.536 - FACILITY AND DESIGN STANDARDS: DESIGN STANDARDS FOR FLUORIDATION
Current through August 31, 2023
01. Chemical Feed Equipment and Methods. In addition to the requirements in Section 531, fluoride feed equipment shall meet the following requirements: (3-24-22)
02. Secondary Controls. Secondary control systems for fluoride chemical feed devices shall be provided as a means of reducing the possibility for overfeed; these may include flow or pressure switches or other devices. (3-24-22)
03. Dust Control. Provision must be made for the transfer of dry fluoride compounds from shipping containers to storage bins or hoppers in such a way as to minimize the quantity of fluoride dust which may enter the room in which the equipment is installed. The enclosure shall be provided with an exhaust fan and dust filter which places the hopper under a negative pressure. Air exhausted from fluoride handling equipment shall discharge through a dust filter to the outside atmosphere of the building. (3-24-22)