Section 58.01.01.595 - SUBMERGED FILL REQUIREMENTS

Universal Citation: ID Admin Code 58.01.01.595

Current through August 31, 2023

The owner or operator must only load gasoline into underground storage tanks at the facility by utilizing submerged filling. (3-28-23)

01. Installed On or Before November 9, 2006. Submerged fill pipes installed on or before November 9, 2006, must be no more than twelve (12) inches from the bottom of the storage tank. (3-28-23)

02. Installed After November 9, 2006. Submerged fill pipes installed after November 9, 2006, must be no more than six (6) inches from the bottom of the storage tank. (3-28-23)

Disclaimer: These regulations may not be the most recent version. Idaho may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.