Hawaii Administrative Rules
Title 6 - DEPARTMENT OF BUDGET AND FINANCE
Division - PUBLIC UTILITIES COMMISSION
Chapter 77 - TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE; MINIMUM SAFETY STANDARDS
Subchapter 6 - MINIMUM SAFETY STANDARDS - DESIGN OF PIPELINE COMPONENTS
Section 6-77-64 - Vaults: sealing, venting, and ventilation

Universal Citation: HI Admin Rules 6-77-64

Current through August, 2024

Each underground vault or closed top pit containing either a pressure regulating or reducing station, or a pressure limiting or relieving station, must be sealed, vented or ventilated, as follows:

(1) When the internal volume exceeds 200 cubic feet:

(A) The vault or pit must be ventilated with two ducts, each having at least the ventilating effect of a pipe four inches in diameter;

(B) The ventilation must be enough to minimize the formation of combustible atmosphere in the vault or pit; and

(C) The ducts must be high enough above grade to disperse any gas-air mixtures that might be discharged;

(2) When the internal volume is more than seventy five cubic feet but less than 200 cubic feet:

(A) If the vault or pit is sealed, each opening must have a tight fitting cover without open holes through which an explosive mixture might be ignited, and there must be a means for testing the internal atmosphere before removing the cover;

(B) If the vault or pit is vented, there must be a means of preventing external sources of ignition from reaching the vault atmosphere; or

(C) If the vault or pit is ventilated, paragraph (1) or (3) applies;

(3) If a vault or pit covered by paragraph (2) is ventilated by openings in the covers or gratings and the ratio of the internal volume, in cubic feet, to the effective ventilating area of the cover or grating, in square feet, is less than twenty to one, no additional ventilation is required.

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.