Hawaii Administrative Rules
Title 6 - DEPARTMENT OF BUDGET AND FINANCE
Division - PUBLIC UTILITIES COMMISSION
Chapter 77 - TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE; MINIMUM SAFETY STANDARDS
Subchapter 5 - MINIMUM SAFETY STANDARDS - PIPE DESIGN
Section 6-77-37 - Design of plastic pipe
Universal Citation: HI Admin Rules 6-77-37
Current through August, 2024
The design pressure for plastic pipe is determined in accordance with the following formula, subject to the limitations of section 6-77-38:
P = Design pressure, gage, kPa (psi).
S = For thermoplastic pipe the long-term hydrostatic strength determined in accordance with the listed specification at a temperature equal to 23E C (73E F), 38E C (100E F), 49E C (120E F), or 60E C (140E F) for reinforced thermosetting plastic pipe, 75,800 kPa (11,000 p.s.i.).
t = Specified wall thickness, mm (in.).
D = Specified outside diameter, mm (in.).
Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.