Section 6-77-32 - Design factor (F) for steel pipe

Universal Citation: HI Admin Rules 6-77-32

Current through August, 2024

(a) Except as otherwise provided in subsections (b), (c), and (d), the design factor to be used in the design formula in section 6-77-29 is determined in accordance with the following table:

Class location | Design factor (F)
1................................ | 0.72
2................................ | 0.60
3................................ | 0.50
4................................ | 0.40

(b) A design factor of 0.60 or less must be used in the design formula in section 6-77-29 for steel pipe in Class 1 locations that:

(1) Crosses the right-of-way of an unimproved public road, without a casing;

(2) Crosses without a casing, or makes a parallel encroachment on the right-of-way of either a hard surfaced road, a highway, a public street, or a railroad;

(3) Is supported by a vehicular, pedestrian, railroad, or pipeline bridge; or

(4) Is used in a fabricated assembly, (including separators, mainline valve assemblies, cross connections, and river crossing headers) or is used within five pipe diameters in any direction from the last fitting of a fabricated assembly, other than a transition piece or an elbow used in place of a pipe bend which is not associated with a fabricated assembly.

(c) For Class 2 locations, a design factor of 0.50, or less, must be used in the design formula in section 6-77-29 for uncaused steel pipe that crosses the right of way of a hard surfaced road, a highway, a public street, or a railroad.

(d) For Class 1 and Class 2 locations, a design factor of 0.50, or less, must be used in the design formula in section 6-77-29 for:

(1) Steel pipe in a compressor station, regulating station, or measuring station; and

(2) Steel pipe, including a pipe riser, on a platform located offshore or in inland navigable waters.

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.