Current through August, 2024

(a) Each cast-iron caulked bell and spigot joint that is subject to pressures of 25 p.s.i.g. or more must be sealed with:

(1) A mechanical leak clamp; or

(2) A material or device which:
(A) Does not reduce the flexibility of the joint;

(B) Permanently bonds, either chemically or mechanically, or both, with the bell and spigot metal surfaces or adjacent pipe metal surfaces; and

(C) Seals and bonds in a manner that meets the strength, environmental, and chemical compatibility requirements of section 6-77-20(1) and (2) and section 6-77-41.

(b) Each cast iron caulked bell and spigot joint that is subject to pressures of less than 25 p.s.i.g. and is exposed for any reason, must be sealed by a means other than caulking.

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.