Section 6-77-185 - Test requirements for reinstating service lines
Universal Citation: HI Admin Rules 6-77-185
Current through August, 2024
(a) Except as provided in subsection (b), each disconnected service line must be tested in the same manner as a new service line, before being reinstated.
(b) Each service line temporarily disconnected from the main must be tested from the point of disconnection to the service line valve in the same manner as a new service line, before reconnecting. However, if provisions are made to maintain continuous service, such as by installation of a bypass, any part of the original service line used to maintain continuous service need not be tested.
Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.