Hawaii Administrative Rules
Title 6 - DEPARTMENT OF BUDGET AND FINANCE
Division - PUBLIC UTILITIES COMMISSION
Chapter 77 - TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE; MINIMUM SAFETY STANDARDS
Subchapter 14 - OPERATIONS
Section 6-77-169 - Odorization of gas
Current through August, 2024
(a) A combustible gas in a distribution line must contain a natural odorant or be odorized so that at a concentration in air of one fifth of the lower explosive limit, the gas is readily detectable by a person with a normal sense of smell.
(b) After December 31, 1976, a combustible gas in a transmission line in a Class 3 or Class 4 location must comply with the requirements of subsection (a) unless:
(c) In the concentrations in which it is used, the odorant in combustible gases must comply with the following:
(d) The odorant may not be soluble in water to an extent greater than 2.5 parts to 100 parts by weight.
(e) Equipment for odorization must introduce the odorant without wide variations in the level of odorant.
(f) Each operator shall conduct periodic sampling of combustible gases to assure the proper concentration of odorant in accordance with this section.