Hawaii Administrative Rules
Title 6 - DEPARTMENT OF BUDGET AND FINANCE
Division - PUBLIC UTILITIES COMMISSION
Chapter 77 - TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE; MINIMUM SAFETY STANDARDS
Subchapter 10 - CUSTOMER METERS, SERVICE REGULATORS, AND SERVICE LINES
Section 6-77-110 - Customer meter installations: operating pressure
Universal Citation: HI Admin Rules 6-77-110
Current through August, 2024
(a) A meter may not be used at a pressure that is more than sixty-seven percent of the manufacturer's shell test pressure.
(b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i.g.
(c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than fifty percent of the pressure used to test the meter after rebuilding or repairing.
Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.