Hawaii Administrative Rules
Title 6 - DEPARTMENT OF BUDGET AND FINANCE
Division - PUBLIC UTILITIES COMMISSION
Chapter 77 - TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE; MINIMUM SAFETY STANDARDS
Subchapter 10 - CUSTOMER METERS, SERVICE REGULATORS, AND SERVICE LINES
Section 6-77-107 - Customer meters and regulators: location
Current through August, 2024
(a) Each meter and service regulator, whether inside or outside of a building, must be installed in a readily accessible location and be protected from corrosion and other damage. However, the upstream regulator in a series may be buried.
(b) Each service regulator installed within a building must be located as near as practicable to the point of service line entrance.
(c) Each meter installed within a building must be located in a ventilated place and not less than three feet from any source of ignition or any source of heat which might damage the meter.
(d) Where feasible, the upstream regulator in a series must be located outside the building, unless it is located in a separate metering or regulating building.