Hawaii Administrative Rules
Title 3 - DEPARTMENT OF ACCOUNTING AND GENERAL SERVICES
Building Code Council
State Fire Code
42 - Fire protection systems hose connection

Universal Citation: HI Admin Rules 42
Current through June, 2024

Section 13.1.5.2 is added to read as follows: 13.1.5.2 Fire department hose connections serving standpipe and sprinkler systems shall be located within twenty feet of a fire apparatus access road, not less than eighteen inches and not more than four feet above grade, or as approved by the AHJ. Appropriate identification signs shall be provided as required by the AHJ.

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.