Hawaii Administrative Rules
Title 3 - DEPARTMENT OF ACCOUNTING AND GENERAL SERVICES
Building Code Council
State Fire Code
112 - Commercial cooking extinguishing system inspection, testing, and maintenance reports
Universal Citation: HI Admin Rules 112
Current through June, 2024
Section 50.5.2 is amended by adding Sections 50.5.2.8.2 and 50.5.2.8.3 to read as follows:
50.5.2.8.2 An inspection, test, and maintenance report entitled "Commercial Cooking Extinguishing System Inspection, Testing and Maintenance Report" or similar report available on the State Fire Council's website and approved by the AHJ shall be provided to the property owner or agent within fourteen days after the test.
50.5.2.8.3 An electronic copy of the unsatisfactory test report shall be submitted to the AHJ within five working days. The AHJ shall determine if the submittal of a satisfactory test report will be required.
Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.