Chapter 224.1 - PRESSURE VESSELS
Section 12-224.1-1 - Scope

Universal Citation: HI Admin Rules 12-224.1-1

Current through August, 2024

The requirements in this section shall apply to pressure vessels, except for the exemptions in section 12-220-2.1 (c)(3) and (4), and is not limited to the following:

(1) All unfired pressure vessels with design pressure exceeding fifteen (15) psi or five (5) cubic feet in volume;

(2) Hot water storage tanks with a nominal water containing capacity greater than 120 gallons;

(3) Unfired autoclaves greater than five (5) cubic feet in volume regardless of operating pressure;

(4) Fired or self-contained sterilizers, jacketed kettles, steam cookers, and autoclaves exceeding a heat input of three (3.0) kw or a volume of one and a half (1.5) cubic feet;

(5) Unfired jacketed kettles with a cooking capacity of forty (40) gallons or more;

(6) Heat exchangers with a heat input exceeding 200,000 Btu/H or five (5) cubic feet in volume;

(7) Hydro pneumatic tanks exceeding one hundred twenty 120 gallons in volume;

(8) Expansion tanks exceeding five (5) cubic feet in volume for hot water heating system; and

(9) Pressure Vessels for Human Occupancy (PVHOs).

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.