Hawaii Administrative Rules
Title 12 - DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS
Subtitle 8 - HAWAII OCCUPATIONAL SAFETY AND HEALTH DIVISION
Part 10 - BOILER AND PRESSURE VESSEL
Chapter 223.1 - HEATING BOILERS - STEAM HEATING BOILERS, HOT-WATER HEATING BOILERS, HOT-WATER SUPPLY BOILERS, AND POTABLE WATER HEATERS
Section 12-223.1-7 - Instruments, fittings, and controls
Universal Citation: HI Admin Rules 12-223.1-7
Current through August, 2024
(a) The following shall apply to steam heating boilers:
(1)
Gages. The following shall apply to gages:
(A) Each steam boiler shall have a steam
gage, or a compound steam gage connected to its steam space or to its water
column or to its steam connection. The gage or connection shall contain a
siphon or equivalent device that will develop and maintain a water seal that
will prevent steam from entering the gage tube. The connection shall be so
arranged that the gage cannot be shut off from the boiler except by a cock
placed in the pipe at the gage and provided with a tee-handle or lever-handle
arranged to be parallel to the pipe in which it is located when the cock is
open. The connections to the boiler shall be not less than NPS 1/4. Where steel
or wrought iron pipe or tubing is used, the connection and external siphon
shall be not less than NPS 1/2. The minimum size of a siphon, if used, shall be
NPS 1/4. Ferrous and nonferrous tubing having inside diameters at least equal
to that of standard pipe sizes listed above may be substituted for pipe;
and
(B) The scale on the dial of a
steam boiler gage shall be graduated to not less than thirty (30) psig nor more
than sixty (60) psig. The travel of the pointer from zero (0) psig to thirty
(30) psig pressure shall be at least three (3) inches;
(2) Water gage glasses. The following shall
apply to water gage glasses:
(A) Each steam
boiler shall have one or more water-gage glasses attached to the water column
or boiler by means of valved fittings not less than NPS 1/2, with the lower
fitting provided with a drain valve of a type having an unrestricted drain
opening not less than NPS 1/4 to facilitate cleaning. Gage glass replacement
shall be possible under pressure. Water glass fittings may be attached directly
to a boiler. Heating boilers having an internal vertical height of less than
ten (10) inches should be equipped with a water level indicator of the glass
bulls-eye type provided the indicator is of sufficient size to show the water
at both normal operating and low-water cutoff levels;
(B) The lowest visible part of the water-gage
glass shall be at least one (1) inch above the lowest permissible water level
recommended by the boiler manufacturer. With the boiler operating at this
lowest permissible water level, there shall be no danger of overheating any
part of the boiler;
(C) In electric
heating boilers of the submerged electrode type, the water-gage glass shall be
so located to indicate the water levels both at startup and under maximum steam
load conditions as established by the manufacturer;
(D) In electric heating boilers of the
resistance element type, the lowest visible part of the water gage shall be
located at least one (1) inch above the lowest permissible water level
specified by the manufacturer. Each electric boiler of this type shall also be
equipped with an automatic low-water cutoff on each boiler so located as to
automatically cut off the power supply to the heating elements before the
surface of the water falls below the visible part of the glass;
(E) Tubular water glasses on electric heating
boilers having a normal water content not exceeding 100 gallons shall be
equipped with a protective shield; and
(F) Transparent material other than glass may
be used for the water gage provided that the material will remain transparent
and has proved suitable for the pressure, temperature, and corrosive conditions
expected in service;
(3)
Water column and water level control pipes.
The following shall apply to water column and water level control pipes:
(A) The minimum size of
ferrous or nonferrous pipes connecting a water column to a steam boiler shall
be NPS 1. No outlet connections, except for damper regulator, feedwater
regulator, steam gages, or apparatus that does not permit the escape of any
steam or water except for manually operated blowdown, shall be attached to a
water column or the piping connecting a water column to a boiler for
introduction of feedwater into a boiler. If the water column, gage glass,
low-water fuel cutoff, or other water level control device is connected to the
boiler by pipe and fittings, no shutoff valves of any type shall be placed in
such pipe and a cross or equivalent fitting to which a drain valve and piping
may be attached shall be placed in the water piping connection at every right
angle turn to facilitate cleaning and inspection. The water column drain pipe
and valve shall be not less than 3/4-inch diameter; and
(B) The steam connections to the water column
of a horizontal firetube wrought boiler shall be taken from the top of the
shell or the upper part of the head, and the water connection shall be taken
from a point not above the center line of the shell. For a cast-iron boiler,
the steam connection to the water column shall be taken from the top of an end
section or the top of the steam header, and the water connection shall be made
on an end section not less than six (6) inches below the bottom connection to
the water-gage glass;
(4)
Pressure control. The following shall apply to pressure control:
(A) Each automatically fired steam boiler
shall be protected from overpressure by two pressure-operated controls. Each
individual steam boiler or each system of commonly connected steam heating
boilers shall have a control that will cut off the fuel supply when the steam
pressure reaches an operating limit, which shall be less than the maximum
allowable pressure;
(B) Each
individual automatically fired steam boiler shall have a safety limit control,
with a manual reset that will cut off the fuel supply to prevent steam pressure
from exceeding the fifteen (15) psig maximum allowable working pressure of the
boiler. Each control shall be constructed to prevent a pressure setting above
fifteen (15) psig; and
(C) Shutoff
valves of any type shall not be placed in the steam pressure connection between
the boiler and the controls described in subparagraphs (A) and (B). These
controls shall be protected with a siphon or equivalent means of maintaining a
water seal that will prevent steam from entering the control. The connections
to the boiler shall not be less than NPS 1/4, but where steel or wrought iron
pipe or tubing is used, they shall not be less than NPS 1/2. The minimum size
of an external siphon shall be NPS 1/4 or 3/8 inch outside diameter nonferrous
tubing. For manifold connections, the minimum size shall be as specified in the
original code of construction; and
(5) Automatic low-water fuel cutoff and water
feeding devices. The following shall apply to automatic low-water fuel cutoff
and water feeding devices:
(A) Each
automatically fired steam or vapor system boiler shall have an automatic
low-water fuel cutoff so located as to automatically cut off the fuel supply
when the surface of the water falls to the lowest visible part of the
water-gage glass. If a water feeding device is installed, it shall be so
constructed that the water inlet valve cannot feed water into the boiler
through the float chamber and so located as to supply requisite
feedwater;
(B) Such a fuel cutoff
or water feeding device may be attached directly to a boiler. A fuel cutoff or
water feeding device may also be installed in the tapped openings available for
attaching a water glass directly to a boiler, provided the connections are made
to the boiler with nonferrous tees or Y fittings not less than NPS 1/2 between
the boiler and water glass so that the water glass is attached directly and as
close as possible to the boiler; the run of the tee or Y-fitting shall take the
water glass fittings, and the side outlet or branch of the tee or Y-fittings
shall take the fuel cutoff or water feeding device. The ends of all nipples
shall be reamed to full-size diameter;
(C) In addition to the requirements in
subparagraphs (A) and (B), a secondary low-water fuel cutoff with manual reset
shall be provided on each automatically fired steam or vapor system boiler;
and
(D) Fuel cutoffs and water
feeding devices embodying a separate chamber shall have a vertical drain pipe
and a blowoff valve not less than NPS 3/4, located at the lowest point in the
water equalizing pipe connections so that the chamber and the equalizing pipe
can be flushed and the device tested.
(b) Hot-water heating or hot-water supply boilers. The following shall apply to hot-water heating or hot-water supply boilers:
(1) Pressure or altitude gages:
(A) Each hot-water heating or hot-water
supply boiler shall have a pressure or altitude gage connected to it or to its
flow connection in such a manner that it cannot be shut off from the boiler
except by a cock with tee or lever handle, placed on the pipe near the gage.
The handle of the cock shall be parallel to the pipe in which it is located
when the cock is open;
(B) The
scale on the dial of the pressure or altitude gage shall be graduated
approximately to not less than one and a half (1-1/2) nor more than three and a
half (3-1/2) times the pressure at which the safety relief valve is set;
and
(C) Piping or tubing for
pressure or altitude gage connections shall be of nonferrous metal when smaller
than NPS 1;
(2)
Thermometers: each hot-water heating or hot-water supply boiler shall have a
thermometer so located and connected that it shall be easily readable. The
thermometer shall be so located that it shall always indicate the temperature
of the water in the boiler at or near the outlet;
(3) Temperature controls. Each automatically
fired hot-water heating or hot-water supply boiler shall be protected from
over-temperature by two temperature-operated controls. The following shall
apply to automatically fired hot-water heating and hot-water supply boilers:
(A) Each individual hot-water heating or
hot-water supply boiler or each system of commonly connected heating boilers
shall have a control that will cut off the fuel supply when the water
temperature reaches an operating limit, which shall be less than the maximum
allowable temperature; and
(B) Each
individual automatically fired hot-water heating or hot-water supply boiler
shall have a safety limit control with manual reset that will cut off the fuel
supply to prevent the water temperature from exceeding the maximum allowable
temperature at the boiler outlet; and
(4) Low-water fuel cutoff. The following
shall apply to automatically fired hot-water heating boilers:
(A) Each automatically fired hot-water
heating boiler shall have an automatic low-water fuel cutoff with manual reset.
The low-water fuel cutoff shall be designed for hot-water service, and it shall
be so located as to automatically cut off the fuel supply when the surface of
the water falls to the level established in subparagraph (B);
(B) As there is no normal waterline to be
maintained in a hot-water boiler, any location of the low-water fuel cutoff
above the lowest safe permissible water level established by the boiler
manufacturer is satisfactory;
(C)
In lieu of the requirements for low-water fuel cutoffs in subparagraph (A),
heating boilers requiring forced circulation to prevent overheating of the
tubes, coils, or vessel, shall have an accepted flow-sensing or
temperature-sensing device to prevent burner operation at a flow rate
inadequate to protect the boiler unit against overheating at all allowable
firing rates. This safety control(s) shall shut down the burner and prevent
restarting until an adequate flow is restored and shall be independent of all
other controls; and
(D) A means
shall be provided for testing the operation of the external low-water fuel
cutoff without resorting to draining the entire system. Such means shall not
render the device inoperable except as follows: if the means temporarily
isolates the device from the boiler during this testing, it shall automatically
return to its normal position. The connection may be so arranged that the
device cannot be shut off from the boiler except by a cock placed at the device
and provided with a tee or lever-handle arranged to be parallel to the pipe in
which it is located when the cock is open;
(c) Potable water heaters. The following shall apply to potable water heaters:
(1)
Temperature controls. The following shall apply to the temperature controls of
potable water heaters:
(A) Each individual
automatically fired water heater, in addition to the operating control used for
normal water heater operation, shall have a separate high limit temperature
actuated combustion control that will automatically cut off the fuel supply.
The temperature range of the high limit temperature actuated control shall not
allow a setting over 210 degrees Fahrenheit;
(B) Gas-fired water heaters: the high limit
temperature control when actuated shall shut off the fuel supply with a shutoff
means other than the operating control valve. Separate valves may have a common
body;
(C) Electrically heated water
heaters: the high limit temperature control when actuated shall cut off all
power to the operating controls;
(D) Oil-fired water heaters: the high limit
temperature control when actuated shall cut off all current flow to the burner
mechanism; and
(E) Indirect water
heating systems: the high limit temperature control when activated shall cut
off the source of heat;
(2) Pressure or altitude gages. The following
shall apply to pressure or altitude gages:
(A) Each potable water heater shall have a
pressure or altitude gage connected to it or to its flow connection in such a
manner that it cannot be shut off from the boiler except by a cock with tee or
lever handle placed on the pipe near the gage. The handle of the cock shall be
parallel to the pipe in which it is located when the cock is open;
(B) The scale on the dial of the pressure or
altitude gage shall be graduated approximately to not less than one and a half
(1-1/2) nor more than three (3) times the maximum allowable working pressure;
and
(C) Piping or tubing for
pressure or altitude gage connections shall be of nonferrous metal when smaller
than 1-inch pipe size;
(3) Thermometers: each installed water heater
shall have a thermometer so located and connected that it shall be easily
readable. The thermometer shall be so located that it shall always indicate the
temperature of the water in the water heater at or near the outlet;
and
(4) Flow-sensing device: potable
water heaters requiring forced circulation to prevent overheating of the tubes,
coils, or vessel should have an acceptable flow-sensing device or
temperature-sensing device to prevent burner operation at a flow rate
inadequate to protect the water heater unit against overheating at all
allowable firing rates. This safety controls shall shut down the burner and
prevent restarting until an adequate flow is restored and shall be independent
of all other controls.
Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.