(a) The following shall apply to all heating boilers:

(1) All heating boilers in operation in this jurisdiction shall have a current and valid operating permit issued to a specific location by the department;

(2) Changes in location or ownership shall require department notification and may require reinspection;

(3) Heating boilers shall bear the ASME Code Symbol Stamp "H", "HLW" or ASME certification mark with "H", "HLW" designator and the NB registration number;

(4) ASME and NB stamping shall be legible and not be concealed by insulation or paint; and

(5) Upon completion of the installation of a new heating boiler, it shall be marked by the inspector employed by the department with a state serial number, consisting of letters and figures to be not less than 5/16 inch in height and arranged as HHB####-Year.

(b) Steam heating boilers not in use for a period of one year or more, for any reason, shall be inspected internally and externally before being placed into operation.

(c) Replacement of an existing heating boiler shall be in accordance with the requirements for new boiler installations.

(d) Replacement of a heating boiler at an existing location with a used or secondhand boiler shall comply with the requirements of new boiler installations. The following shall apply to used or secondhand heating boilers:

(1) Used or secondhand heating boilers when installed in this jurisdiction, shall be equipped with fittings and appurtenances that comply with new installations; and

(2) Weld repairs, alterations, and inspection records shall be submitted with the installation application for used or secondhand heating boilers.

(e) Replacement or repairs to boiler fittings, appurtenances or appliances, controls and safety devices, shall comply with the requirements for new installations and applicable ASME BPVC and NBIC sections.

(f) Galvanized pipe shall not be used for steam supply and blowdown piping.

(g) State specials: applicable provisions include sections 12-220-2(b) and 12-220-16 (e) (6).

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.