Hawaii Administrative Rules
Title 12 - DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS
Subtitle 8 - HAWAII OCCUPATIONAL SAFETY AND HEALTH DIVISION
Part 10 - BOILER AND PRESSURE VESSEL
Chapter 223.1 - HEATING BOILERS - STEAM HEATING BOILERS, HOT-WATER HEATING BOILERS, HOT-WATER SUPPLY BOILERS, AND POTABLE WATER HEATERS
Section 12-223.1-12 - Heating boiler room and operating area
Current through August, 2024
(a) The following shall apply to the care of heating boiler rooms:
(b) Foundation, supports, and settings. Each heating boiler and its associated piping must be safely supported. Design of supports, foundations, and settings shall consider vibration (including seismic where necessary), movement (including thermal expansion and contraction), and loadings (including the weight of the fluid in the system during a pressure test) in accordance with jurisdictional requirements, manufacturers recommendations, and other industry standards, as applicable.
(c) Exit. Two means of exit shall be provided for equipment rooms exceeding 500 square feet floor area and containing one or more heating boilers having a combined fuel capacity of 1,000,000 Btu per hour or more. Each elevation shall be provided with at least two means of exit, each to be remotely located from the other. A platform at the top of a single heating boiler is not considered an elevation.
(d) The following shall apply to ladders and runways:
(e) Drains. At least one floor drain shall be installed in the equipment room. Drains receiving blowdown water should be connected to the sanitary sewer by way of an acceptable blowdown tank or separator or an air gap that will allow the blowdown water to cool to at least 140 degrees Fahrenheit and reduce the pressure to five (5) psig or less.
(f) Water. The following shall apply to water: