(a) Water level
indicators. The following shall apply to water level indicators:
(1) Each steam boiler having a fixed
waterline shall have at least one water gage glass, except that boilers
operated at pressures over 400 psig shall be provided with two water gage
glasses that may be connected to a single water column, or connected directly
to the drum. The gage glass and pipe connections shall be not less than NPS
1/2. Each water gage glass shall be equipped with a drain valve;
(2) The lowest visible water level in a gage
glass shall be at least two inches above the lowest permissible water level as
determined by the manufacturer;
(3)
Gage glasses shall be connected directly to the shell or drum of the boiler or
to an intervening water column;
(4)
The lower edge of the steam connection between a water column, gage glass, or
water level sending device in the boiler, shall not fall below the highest
visible water level in the gage glass. In addition, there shall be no sag of
offset in the piping that will permit accumulation of water;
(5) The upper edge of the water connection
between water column, gage glass, or water level sensing device in the boiler,
shall not be above the lowest visible water level in the gage glass. In
addition, no part of the pipe connection shall be above the point of connection
at the water column;
(6) For
installations where the water-gage glass or glasses are not easily viewed by
the operator, consideration should be given to install a method of remote
transmission of the water level to the operating floor;
(7) Boilers of the horizontal firetube type
shall be so set that when the water is at the lowest reading in the water-gage
glass, it shall be three (3) inches above the lowest permissible water level as
determined by the manufacturer. Horizontal firetube boilers that do not exceed
sixteen (16) inches in inside diameter shall have the lowest visible level in
the gage glass at least one (1) inch above the lowest permissible level as
determined by the manufacturer,
(8)
Each water-gage glass shall be equipped with a top and a bottom shutoff valve
of such through-flow construction as to prevent blockage by deposits of
sediment and to indicate by the position of the operating mechanism whether
they are in the open or closed position. The pressure-temperature rating shall
be at least equal to that of the lowest set pressure of any safety valve on the
boiler drum and the corresponding saturated stream pressure; provided that:
(A) Boilers having a maximum allowable
working pressure of four hundred (400) psi or less shall always have at least
one gage glass in service; or
(B)
Boilers having maximum allowable working pressure greater than 400 psi shall
always have two gage glasses in service:
(i)
When two gage glasses are required, both may connect to a single water
column;
(ii) Instead of one of the
two required gage glasses, two independent remote water level indicators (two
discrete systems that continuously measure, transmit, and display water level)
may be provided. In addition, minimum water levels shall be clearly marked;
(iii) When both remote level
indicators are in reliable operation, the remaining gage glass may be shut off,
but shall be maintained in serviceable condition; and
(iv) When the water level in at least one
gage glass is not readily visible to the operator in the area where control
actions are initiated, either a fiber optic cable (with no electrical
modification of the optical signal) or mirrors shall be provided to transfer
the optical image of the water level to the control area.
Provided that alternatively any combination of either an
independent remote water level indicator or an independent continuous
transmission and display of an image of the water level in a gage glass may be
used. If the latter is used, then the display of a remote water level indicator
shall have a clearly marked minimum water level reference at least two (2)
inches above the lowest permissible water level, as determined by the
manufacturer;
(9) Gage glass assemblies with multiple
sections, whether of tubular or other construction, shall:
(A) Ensure a one-foot overlap of all
adjoining sections so the water level is visible; or
(B) Ported or reflex gages using refractive
light to aid determination of water level may omit the requirement of
overlapping sections;
(10) The gage class cock connections shall
not be less than one-half (1/2) of an inch NPS;
(11) Each gage glass, externally mounted
water level, or water level controlling device shall be fitted with a drain
cock or valve having an unrestricted drain opening of not less than one-fourth
(1/4) of an inch in diameter to facilitate cleaning;
(12) Connections for gage glasses connected
directly to the boiler or to an intervening water column shall be at least NPS
one-half (1/2);
(13) Connections
from the boiler to a remote water level indicator shall be at least NPS
three-fourths (3/4), including the isolation valve; and from there to the
remote level indicator at least one-half (1/2) of an inch in OD
tubing;
(14) Water level
connections shall be completely independent of other connections for any
function other than water level indication; and
(15) Electric steam boilers shall have at
least one water-gage glass. On electrode type electric boilers, the gage glass
shall be located as to indicate the water levels both at startup and maximum
steam load conditions, as established by the boiler manufacturer. On resistance
element type electric steam boilers, the lowest visible part of the gage glass
shall be located at least 1 inch above the lowest permissible water level
established by the boiler manufacturer.
(b) Low-water fuel cutoffs and water feeding
devices. The following shall apply to low-water fuel cutoffs and water feeding
devices:
(1) Each automatically fired steam or
vapor system boiler shall have an automatic low-water fuel cutoff device so
located as to automatically cut off the fuel supply when the surface of the
water falls to the lowest visible part of the water-gage glass. If a water
feeding device is installed, it shall be so constructed that the water inlet
valve cannot feed water into the boiler through the float chamber and so
located as to supply requisite feedwater; provided that such a fuel cutoff or
water feeding device may be attached directly to the boiler. A fuel cutoff or
water feeding device may also be installed in the tapped openings available for
attaching a water glass directly to the boiler, provided the connections are
made to the boiler with nonferrous tees or Ys not less than NPS one-half (1/2)
inch between the boiler and water glass so that the water glass is attached
directly and as close as possible to the boiler, the run of the tee or Y shall
take the water glass fittings, and the side outlet or branch of the tee or Y
shall take the fuel cutoff or water feeding device. The ends of all nipples
shall be reamed to full-size diameter. In addition, a secondary low-water fuel
cutoff with manual reset shall be provided on each automatically fired steam or
vapor system boiler;
(2)
Functioning of the lower of the two controls shall cause safety shutdown and
lockout. The manual reset may be incorporated in the lower cutoff control.
Where a reset device is separate from the low-water fuel cutoff, a means shall
be provided to indicate actuation of the low-water fuel cutoff. The manual
reset device may be of the instantaneous type or may include a time delay of
not more than three (3) minutes after the fuel has been cut off;
(3) The fuel cutoff device may be inserted
internally or attached externally to the boiler. An external cutoff device may
be attached on piping connecting a water column to the boiler or combined with
a water column;
(4) Water column
piping and connections shall be at least NPS 1 (DN 25). If the low-water fuel
cutoff is connected to the boiler by pipe or fittings, no shutoff valves of any
type shall be placed in such piping. The steam and water connections to a water
column shall be readily accessible for internal inspection and cleaning. Some
acceptable methods of meeting this requirement are by providing a cross-fitting
with a back outlet at each right-angle turn to permit inspection and cleaning
in both directions or by using pipe bends or fittings of a type that does not
leave an internal shoulder or pocket in the pipe connection and with a radius
of curvature that will permit the passage of a rotary cleaner. Fuel cutoff
devices embodying a separate chamber shall have a vertical drainpipe and
blowoff valve, not less than NFS 3/4, located at the lowest point of the
chamber or water-equalizing pipe connections, so that the chamber and the
equalizing pipe can be flushed and the device tested;
(5) Fuel cutoffs and water feeding devices
embodying a separate chamber shall have a vertical drainpipe, extended to a
safe point of discharge, and a blowoff valve not less than NFS 3/4, located at
the lowest point in the water equalizing pipe connections so that the chamber
and the equalizing pipe can be flushed and the device tested;
(6) Each miniature boiler, except electric
boilers of the electrode type, shall have at least one low-water fuel cutoff
device;
(7) Each electric steam
boiler of the resistance element type shall be equipped with an automatic
low-water cutoff so located as to automatically cut off the power supply to the
heating elements before the surface of the water falls below the visible part
of the glass. No low-water cutoff is required for electrode-type boilers;
(8) These devices shall be
installed in such a manner that they cannot be rendered inoperative by the
manipulation of any manual control or regulating apparatus;
(9) In boilers with a fixed water line, the
low-water fuel cutoff devices shall be tested regularly by lowering the water
level sufficiently to shut off the fuel supply to the burner when the water
level reaches the lowest safe level for operation. Boilers that do not have a
fixed water line shall be equipped with a flow sensing device, thermal couple
or expansion ring that is listed by a nationally recognized testing agency to
prevent burner operation at a flow rate inadequate to protect the boiler unit
against overheating;
(10) Boilers
with single drain electronic solenoid valve shall be fitted with a manual
by-pass drain line to facilitate testing of the low-water cutoff safety
device;
(11) The low-water cutoff
shall be rated for a pressure and temperature equal to or greater than the MAWP
and temperature of the boiler;
(12)
For high-temperature water boilers requiring forced flow circulation, an
approved flow sensing device shall be installed on the outlet, as close to the
boiler as possible;
(13) When a
low-water fuel cutoff and feedwater pump control is combined in a single
device, an additional separate low-water fuel cutoff shall be installed. The
additional control shall be wired in series electrically with the existing
low-water fuel cutoff;
(14) When a
low-water fuel cutoff is housed in either the water column or a separate
chamber it shall be provided with a blowdown pipe and valve not less than 3/4
inch NPS. The arrangement shall be such that when the water column is blown
down, the water level in it will be lowered sufficiently to activate the
lower-water fuel cutoff device; and
(15) If a water feed device is utilized, it
shall be constructed to prevent feedwater from entering the boiler through the
water column or separate chamber of the low-water fuel cutoff.
(c) Pressure gages. The following
shall apply to pressure gages:
(1) Each steam
boiler shall have a pressure gage connected to the steam space or to the steam
connection to the water column. When a pressure-reducing valve is installed in
the steam supply piping, a pressure gage shall be installed on the low pressure
side of the pressure-reducing valve;
(2) The dial range shall not be less than 1.5
times and no greater than approximately two times the pressure at which the
lowest pressure relief valve is set;
(3) For a steam boiler, the gage or
connection shall contain a siphon or equivalent device that will develop and
maintain a water seal that will prevent steam from entering the gage tube. A
valve or cock shall be placed in the gage connection adjacent to the gage. An
additional valve or cock should be located near the boiler providing it is
locked or sealed in the open position. No other shut-off valves shall be
located between the gage and the boiler; and
(4) Pressure gage connections shall be
suitable for the maximum allowable working pressure and temperature, but if the
temperature exceeds 406°F, brass or copper pipe or tubing shall not be
used. The connections to the boiler, except for the siphon, if used, shall not
be less than NPS 1/4 inch Where steel or wrought iron pipe or tubing is used,
it shall not be less than 1/2 inch inside diameter. The minimum size of a
siphon, if used, shall be 1/4 inch inside diameter.
(d) Water columns. The following are
requirements for water columns:
(1) The water
column shall be directly connected to the boiler. Outlet connections (except
for damper regulator, feedwater regulator, low-water fuel cutoff, drains, steam
gages, or such apparatus that does not permit the escape of an appreciable
amount of steam or water) should not be placed on the piping that connects the
water column to the boiler;
(2)
Straight-run globe valves of the ordinary type shall not be used on piping that
connects the water column to the boiler. Where water columns are seven (7) feet
or more above the floor level, adequate means for operating gage cocks or
blowing out the water glass shall be provided;
(3) When automatic shutoff valves are used on
piping that connects the water column to the boiler, they shall conform to the
requirements of the code of construction for the boiler;
(4) When shutoff valves are used on the
connections to a water column, they shall be either outside-screw and yoke or
lever-lifting-type gate valves or stop cocks with levers permanently fastened
thereto and marked in line with their passage, or of such other through-flow
constructions to prevent stoppage by deposits of sediment and to indicate by
the position of the operating mechanism whether they are in open or closed
position; provided that the valves or cocks shall be locked or sealed open;
(5) The water column shall be
fitted with a drain cock or drain valve of at least three-fourths (3/4) of an
inch nominal pipe size and shall be piped to a safe point of
discharge;
(6) Connections from the
boiler to the water column shall be at least NPS 1;
(7) The steam and water connections to a
water column or a water gage glass shall be readily accessible for internal
inspection and cleaning; and
(8)
Shutoff valves shall not be used in the pipe connections between a boiler and a
water column, or between a boiler and the shutoff valves required for the gage
glass, except:
(A) Outside screw-and-yoke or
lever-lifting-type gate valves or stopcocks with lever permanently fastened
thereto and marked in line with their passage; and
(B) Another through-flow construction that
prevents stoppage by deposits of sediment, and to indicate by the position of
the operating mechanisms whether they are in open or closed position. These
valves or cocks shall be locked or sealed open. Where stopcocks are used, they
shall be of a type with the plug held in place by a guard or gland.