Current through August, 2024
(a) Feedwater
volume. The source of feedwater shall be capable of supplying a sufficient
volume of water as determined by the boiler manufacturer to prevent damage to
the boiler when all the safety relief valves are discharging at full capacity.
(b) Feedwater connection. The
following shall apply to feedwater connection:
(1) To prevent thermal shock, feedwater shall
be introduced into a boiler in such a manner that the water will not be
discharged directly against surfaces exposed to high temperature gases or to
direct radiation from the flame;
(2) For boiler operating pressures of 400
psig or higher, the feedwater inlet through the drum shall be fitted with
shields, sleeves, or other suitable means to reduce the effects of temperature
differentials in the shell or head;
(3) Feedwater other than condensate return
shall not be introduced through the blowoff;
(4) Boilers having more than 500 square feet
of water heating surface shall have at least two means of supplying feedwater.
For boilers that are fired with solid fuel not in suspension, and boilers whose
setting or heat source can continue to supply sufficient heat to cause damage
to the boiler if the feedwater supply is interrupted, one such means of
supplying feedwater shall not be subject to the same interruption as the first
method. Boilers fired by gaseous, liquid, or solid fuel in suspension may be
equipped with a single means of supplying feedwater, provided means are
furnished for the immediate removal of heat input if the supply of feedwater is
interrupted;
(5) For boilers having
a water heating surface of not more than 100 square feet, the feedwater piping
and connection to the boiler shall not be smaller than NPS 1/2. For boilers
having a water heating surface more than 100 square feet, the feedwater piping
and connection to the boiler shall not be less than NPS 3/4;
(6) Electric boiler feedwater connections
shall not be smaller than NPS 1/2; and
(7) High-temperature water boilers shall be
provided with means of adding water to the boiler or system while under
pressure.
(c) Pumps. The
following shall apply to pumps:
(1) Boiler
feedwater pumps shall have discharge pressure more than the highest set
pressure relief valve to compensate for frictional losses, entrance losses,
regulating valve losses, and normal static head, etc. Each source of feedwater
shall be capable of supplying feedwater to the boiler at a minimum pressure of
three per cent (3%) higher than the highest setting of any pressure relief
valve on the boiler proper. Detailed engineering evaluation of the pump
selection shall be performed and available for review. Table 2.5.1.3 is a
guideline for estimating feedwater pump differential;
TABLE 2.5.1.3
GUIDE FOR FEEDWATER PUMP DIFFERENTIAL
Boiler Pressure
|
Boiler Feedwater Pump Discharge Pressure
|
psig
|
(MPa)
|
psig
|
(MPa)
|
200
|
(1.38)
|
250
|
(1.72)
|
400
|
(2.76)
|
475
|
(3.28)
|
800
|
(5.52)
|
925
|
(6.38)
|
1,200
|
(8.27)
|
1,350
|
(9.31)
|
(2)
For forced-flow steam generators with no fixed steam or water line, each source
of feedwater shall be capable of supplying feedwater to the boiler at a minimum
pressure equal to the expected maximum sustained pressure at the boiler inlet
corresponding to operation at maximum designed steaming capacity with maximum
allowable pressure at the superheater outlet; and
(3) Control devices may be installed on
feedwater piping to protect the pump against overpressure.
(d) Feedwater valves. The following shall
apply to feedwater valves:
(1) The feedwater
piping shall be provided with a check valve and a stop valve. The stop valve
shall be located between the check valve and the boiler;
(2) When two or more boilers are fed from a
common source, there shall also be a globe or regulating valve on the branch to
each boiler located between the check valve and the feedwater source;
(3) When the feedwater piping is divided into
branch connections and all such connections are equipped with stop and check
valves, the stop and check valve in the common source may be omitted;
(4) On single boiler-turbine unit
installations, the boiler feedwater stop valve may be located upstream from the
boiler feedwater check valve;
(5)
If a boiler is equipped with duplicate feedwater supply arrangements, each such
arrangement shall be equipped as required by these rules;
(6) A check valve shall not be a substitute
for a stop valve;
(7) A combination
feedwater stop-and-check valve in which there is only one seat and disk and a
valve stem is provided to close the valve when the stem is screwed down shall
be considered only as a stop valve; a separate check valve shall also be
installed;
(8) Whenever globe
valves are used on feedwater piping, the inlet shall be under the disk of the
valve;
(9) Stop valves and check
valves shall be placed on the inlet of economizers or feedwater-heating
devices; and
(10) The recirculating
return line for a high-temperature water boiler shall be provided with the stop
valve, or valves, required for the main discharge outlet on the
boiler.
(e) Electrical. A
disconnecting means capable of being locked in the open position shall be
installed at an accessible location at the boiler so that the boiler can be
disconnected from all sources of potential. This disconnecting means shall be
an integral part of the boiler or adjacent to it.
(f) Wiring. All wiring for controls, heat
generating apparatus, and other appurtenances necessary for the operation of
the boiler or boilers should be installed in accordance with the provisions of
national or international standards and comply with the applicable local
electrical codes.
(g) Remote
emergency shutdown switches. The following shall apply to remote emergency
shutdown switches:
(1) A manually operated
remote shutdown switch or circuit breaker shall be located just outside the
equipment room door and marked for easy identification. Consideration should
also be given to the type and location of the switch to safeguard against
tampering. Where approved by the jurisdiction, alternate locations of remote
emergency switches may be provided;
(2) For equipment rooms exceeding 500 square
feet floor area, or containing one or more boilers having a combined fuel
capacity of 1,000,000 Btu/hr or more, additional manually operated remote
emergency shutdown switches shall be located at suitably identified points of
egress acceptable to the jurisdiction;
(3) Where a boiler is located indoors in a
facility and not in an equipment room, a remote emergency shutdown switch shall
be located within fifty (50) feet of the boiler along the primary egress route
from the boiler area;
(4) For
atmospheric-gas burners and for oil burners where a fan is on the common shaft
with the oil pump, the emergency remote shutdown switches or circuit breakers
must disconnect all power to the burner controls; and
(5) For power burners with detached
auxiliaries, the emergency remote shutdown switches or circuit breakers need
only shut off the fuel input to the burner.