(a) Feedwater
volume. The source of feedwater shall be capable of supplying a sufficient
volume of water as determined by the boiler manufacturer to prevent damage to
the boiler when all the safety relief valves are discharging at full capacity.
(b) Feedwater connection. The
following shall apply to feedwater connection:
(1) To prevent thermal shock, feedwater shall
be introduced into a boiler in such a manner that the water will not be
discharged directly against surfaces exposed to high temperature gases or to
direct radiation from the flame;
(2) For boiler operating pressures of 400
psig or higher, the feedwater inlet through the drum shall be fitted with
shields, sleeves, or other suitable means to reduce the effects of temperature
differentials in the shell or head;
(3) Feedwater other than condensate return
shall not be introduced through the blowoff;
(4) Boilers having more than 500 square feet
of water heating surface shall have at least two means of supplying feedwater.
For boilers that are fired with solid fuel not in suspension, and boilers whose
setting or heat source can continue to supply sufficient heat to cause damage
to the boiler if the feedwater supply is interrupted, one such means of
supplying feedwater shall not be subject to the same interruption as the first
method. Boilers fired by gaseous, liquid, or solid fuel in suspension may be
equipped with a single means of supplying feedwater, provided means are
furnished for the immediate removal of heat input if the supply of feedwater is
interrupted;
(5) For boilers having
a water heating surface of not more than 100 square feet, the feedwater piping
and connection to the boiler shall not be smaller than NPS 1/2. For boilers
having a water heating surface more than 100 square feet, the feedwater piping
and connection to the boiler shall not be less than NPS 3/4;
(6) Electric boiler feedwater connections
shall not be smaller than NPS 1/2; and
(7) High-temperature water boilers shall be
provided with means of adding water to the boiler or system while under
pressure.
(c) Pumps. The
following shall apply to pumps:
(1) Boiler
feedwater pumps shall have discharge pressure more than the highest set
pressure relief valve to compensate for frictional losses, entrance losses,
regulating valve losses, and normal static head, etc. Each source of feedwater
shall be capable of supplying feedwater to the boiler at a minimum pressure of
three per cent (3%) higher than the highest setting of any pressure relief
valve on the boiler proper. Detailed engineering evaluation of the pump
selection shall be performed and available for review. Table 2.5.1.3 is a
guideline for estimating feedwater pump differential;
TABLE 2.5.1.3
GUIDE FOR FEEDWATER PUMP DIFFERENTIAL
Boiler Pressure
|
Boiler Feedwater Pump
Discharge Pressure
|
psig
|
(MPa)
|
psig
|
(MPa)
|
200
|
(1.38)
|
250
|
(1.72)
|
400
|
(2.76)
|
475
|
(3.28)
|
800
|
(5.52)
|
925
|
(6.38)
|
1,200
|
(8.27)
|
1,350
|
(9.31)
|
(2)
For forced-flow steam generators with no fixed steam or water line, each source
of feedwater shall be capable of supplying feedwater to the boiler at a minimum
pressure equal to the expected maximum sustained pressure at the boiler inlet
corresponding to operation at maximum designed steaming capacity with maximum
allowable pressure at the superheater outlet; and
(3) Control devices may be installed on
feedwater piping to protect the pump against overpressure.
(d) Feedwater valves. The following shall
apply to feedwater valves:
(1) The feedwater
piping shall be provided with a check valve and a stop valve. The stop valve
shall be located between the check valve and the boiler;
(2) When two or more boilers are fed from a
common source, there shall also be a globe or regulating valve on the branch to
each boiler located between the check valve and the feedwater source;
(3) When the feedwater piping is divided into
branch connections and all such connections are equipped with stop and check
valves, the stop and check valve in the common source may be omitted;
(4) On single boiler-turbine unit
installations, the boiler feedwater stop valve may be located upstream from the
boiler feedwater check valve;
(5)
If a boiler is equipped with duplicate feedwater supply arrangements, each such
arrangement shall be equipped as required by these rules;
(6) A check valve shall not be a substitute
for a stop valve;
(7) A combination
feedwater stop-and-check valve in which there is only one seat and disk and a
valve stem is provided to close the valve when the stem is screwed down shall
be considered only as a stop valve; a separate check valve shall also be
installed;
(8) Whenever globe
valves are used on feedwater piping, the inlet shall be under the disk of the
valve;
(9) Stop valves and check
valves shall be placed on the inlet of economizers or feedwater-heating
devices; and
(10) The recirculating
return line for a high-temperature water boiler shall be provided with the stop
valve, or valves, required for the main discharge outlet on the
boiler.
(e) Blowoff.
(1) Except for forced-flow steam generators
with no fixed steam or water line, each boiler shall have a blowoff pipe,
fitted with a stop valve, in direct connection with the lowest water space
practicable. When the maximum allowable working pressure of the boiler exceeds
one hundred (100) psig (700 kPa), there shall be two valves
installed;
(2) The blowoff piping
for each electric boiler pressure vessel having a nominal water content not
exceeding one hundred (100) gallons is required to extend through only one
valve;
(3) When two valves are
required, each bottom blowoff pipe shall have two slow-opening valves, or one
quick-opening valve, at the boiler nozzle followed by a slow-opening
valve;
(4) Two independent
slow-opening valves, or a slow-opening valve and quick-opening valve, may be
combined in one body provided the combined fitting is the equivalent of two
independent slow-opening valves, or a slow-opening valve and a quick-opening
valve, and the failure of one to operate cannot affect the operation of the
other;
(5) Straight-run globe
valves or valves where dams or pockets can exist for the collection of sediment
shall not be used;
(6) The blowoff
valve or valves and the pipe and fittings between them and the boiler shall be
of the same size. The minimum size of pipe and fittings shall be NPS 1, except
boilers with one hundred (100) square feet or less of heating surface should be
NPS 3/4. The maximum size of pipe and fittings shall not exceed NPS
2-1/2;
(7) For electric boilers,
the minimum size of blowoff pipes and fittings shall be NPS 1, except for
boilers of two hundred (200) kw input or less where the minimum size should be
NPS 3/4;
(8) Fittings and valves
shall comply with the appropriate national standard except that austenitic
stainless steel and malleable iron are not permitted;
(9) When the maximum allowable working
pressure exceeds one hundred 100 psig, blowoff piping shall be at least
Schedule 80 and the required valves and fittings shall be rated for at least
1.25 times the maximum allowable working pressure of the boiler. When the
maximum allowable working pressure exceeds 900 psig, blowoff piping shall be at
least Schedule 80 and the required valves and fittings shall be rated for at
least the maximum allowable working pressure of the boiler plus 225
psi;
(10) All blowoff piping, when
exposed to furnace heat, shall be protected by fire brick or other heat
resisting material so constructed that the piping may be readily
inspected;
(11) On a boiler having
multiple blowoff pipes, a single master stop valve should be placed on the
common blowoff pipe from the boiler and one stop valve on each individual
blowoff. Either the master valve or the valves on the individual blowoff lines
shall be of the slow-opening type;
(12) The discharge of blowoff pipes shall be
located so as to prevent injury to personnel;
(13) All waterwalls or water screens that do
not drain back into the boiler and integral economizers forming part of a
boiler shall be equipped with blowoff piping and valves conforming to the
requirements of this subsection;
(14) Blowoff piping from a boiler should not
discharge directly into a sewer. A blowoff tank, constructed to the provisions
of a code of construction acceptable to the jurisdiction, shall be used where
conditions do not provide an adequate and safe open discharge;
(15) Galvanized pipe shall not be
used;
(16) Boiler blowoff systems
should be constructed in accordance with the Guide for Blowoff Vessels (NB-27),
which can be found on the National Board website at
www.nationalboard.org;
(17) Where necessary to install a blowoff
tank underground, it shall be enclosed in a concrete or brick pit with a
removable cover so that inspection of the entire shell and heads of the tank
can be made; and
(18) Piping
connections used primarily for continuous operation, such as deconcentrators on
continuous blowdown systems, are not classed as blowoffs; but the pipe
connections and all fittings up to and including the first shutoff valve shall
be equal at least to the pressure requirements for the lowest set pressure of
any safety valve on the boiler drum and with the corresponding saturated-steam
temperature. Further, such connections shall not exceed NPS
2-1/2.
(f) Drains. Each
boiler shall have at least one drainpipe fitted with a stop valve at the lowest
point of the boiler. If the connection is not intended for blowoff purposes, a
single valve is acceptable if it can be locked in the closed position or a
blank flange can be installed downstream of the valve. If the connection is
intended for blowoff purposes, requirements of (e) shall be followed.
(1) For high temperature water boilers, the
minimum size of the drainpipe shall be NPS 1; and
(2) Drainpipes, valves, and fittings within
the same drain line shall be the same size.
(g) Electrical. A disconnecting means capable
of being locked in the open position shall be installed at an accessible
location at the boiler so that the boiler can be disconnected from all sources
of potential. This disconnecting means shall be an integral part of the boiler
or adjacent to it.
(h) Wiring. All
wiring for controls, heat generating apparatus, and other appurtenances
necessary for the operation of the boiler or boilers should be installed in
accordance with the provisions of national or international standards and
comply with the applicable local electrical codes.
(i) Remote emergency shutdown switches. The
following shall apply to remote emergency shutdown switches:
(1) A manually operated remote shutdown
switch or circuit breaker shall be located just outside the equipment room door
and marked for easy identification. Consideration should also be given to the
type and location of the switch to safeguard against tampering. Where approved
by the department, alternate locations of remote emergency switches may be
provided;
(2) For equipment rooms
exceeding 500 square feet floor area, or containing one or more boilers having
a combined fuel capacity of 1,000,000 Btu/hr or more, additional manually
operated remote emergency shutdown switches shall be located at suitably
identified points of egress acceptable to the department;
(3) Where a boiler is located indoors in a
facility and not in an equipment room, a remote emergency shutdown switch shall
be located within fifty (50) feet of the boiler along the primary egress route
from the boiler area;
(4) For
atmospheric-gas burners and for oil burners where a fan is on the common shaft
with the oil pump, the emergency remote shutdown switches or circuit breakers
must disconnect all power to the burner controls;
(5) For power burners with detached
auxiliaries, the emergency remote shutdown switches or circuit breakers need
only shut off the fuel input to the burner; and
(6) When existing boiler installations do not
include remote emergency shutdown switches, it is not required that these
switches be retroactively installed unless required by the
department.