Hawaii Administrative Rules
Title 12 - DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS
Chapter 45.2 - STATE FIR COUNCIL
STATE FIRE CODE
Subchapter 2 - AMENDMENTS TO THE NFPA 1, UFC
Section 12-45.2-73 - Fire department communication system

Universal Citation: HI Admin Rules 12-45.2-73

Current through August, 2024

Section 13.7.2.27.2.2 is amended to read as follows: "A two-way, fire department communication system approved by the AHJ shall be provided for fire department use. A jack or plug receptacle shall be located at the following locations:

1. The emergency command center/central location approved by the AHJ.

2. The designated fire service elevator(s)

3. Each elevator lobby on each floor of the building.

4. Emergency and standby power rooms.

5. The stairwell side of each exit into each required stairway.

The height of the jack or plug receptacle shall be not more than 5 feet and not less than 3 feet above floor level. Portable hand sets in compliance with the following provisions shall be provided by the building owner or management for fire department use:

1. Not less than 10 approved-type portable hand sets shall be stored and maintained in the central control station.

2. Length of cord for portable hand sets shall be provided as recommended and approved by the AHJ.

3. Hand sets approved by the AHJ shall be maintained in an operative condition at all times and shall be replaced or repaired when found to be defective."

Disclaimer: These regulations may not be the most recent version. Hawaii may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.