Current through Reg. 50, No. 249, December 24, 2024
(1) All
pre-engineered systems are to be inspected in accordance with the standards
adopted in rule 69A-21.302, F.A.C.
(2) Whenever a pre-engineered system is
installed, inspected, repaired, maintained or otherwise serviced, the permittee
shall complete an inspection report containing, at a minimum, the information
in paragraphs (a) through (o), in this subsection. One copy shall be signed by
and delivered to the owner, or the representative of the owner of the facility
in which the system was installed. The other copy shall be retained in the fire
equipment dealer's files for a period of not less than three years after the
last inspection.
(a) Location of system;
business name of facility, street address, city, state, zip code, phone number,
and name of the owner or manager;
(b) Whether the report is for an annual
inspection; semi-annual inspection; a recharge; a new installation; or a
renovation;
(c) Where the system is
located in the facility;
(d) Type
of system; name of manufacturer; model number; size of bottles;
(e) Method, style and degree of
actuation;
(f) Reference to drawing
number or page number, and date of the manufacturer's manual;
(g) Date of last hydrostatic test;
(h) Date of last recharge;
(j) Whether fuel shut off is gas or electric
and the size;
(k) A drawing of a
new installation; a first inspection; or whenever changes are made. The drawing
shall include the following as a minimum:
1.
Sizes of the hood, plenum, and ducts.
2. Sizes, types and locations of cooking
appliances.
3. Positions of all
nozzles, identification of nozzles, their distances from the hazards that they
protect.
4. Positions of all
detectors.
5. Diagram of the entire
piping installation.
(l)
Responses to the following questions:
1. Were
the inspection and maintenance performed in accordance with the presently
adopted editions of NFPA (indicate standard(s) used? ("No" answers require an
explanation).
2. Was the system
tagged in accordance with rule
69A-21.303, F.A.C.? ("No"
answers require an explanation).
3.
Were the inspection and maintenance performed in accordance with the
manufacturer's manual and the manufacturer's specifications? ("No" answers
require an explanation).
(m) A comments section to allow for
explanations if necessary.
(n) A
statement that the permittee certifies that he personally inspected the system
and found the conditions to be as indicated on the report.
(o) The permittee's name, signature and
permit number; the date and time of inspection; and the customer's
signature.
Rulemaking Authority 633.104 FS. Law Implemented 633.104,
633.308, 633.216 FS.
New 2-7-89, Amended 10-20-93, 11-21-01, Formerly
4A-21.304.