Florida Administrative Code
69 - DEPARTMENT OF FINANCIAL SERVICES
69A - Division of State Fire Marshal
Chapter 69A-2 - EXPLOSIVES
Section 69A-2.005 - Manufacture; Blasting Agents
Current through Reg. 50, No. 249, December 24, 2024
(1) Buildings or other facilities used for mixing blasting agents, including mobile equipment, shall be located, with respect to inhabited buildings, passenger railroads and public highways, in accordance with the American Table of Distances as set forth in paragraph 69A-2.006(5)(a), F.A.C.
(2) Buildings used for the mixing of blasting agents shall conform to the requirements of these Rules and Regulations, unless otherwise specifically approved by the State Fire Marshal.
(3) The design of the mixer shall minimize the possibility of frictional heating, compaction, and especially, confinement. Bearings and gears shall be protected against the accumulation of oxidizer dust. All surfaces shall be accessible for cleaning. Mixing and packaging equipment shall be constructed of materials compatible with the fuel-oxidizer composition.
(4) The sensitivity of the blasting agent shall be determined by means of a No. 8 test blasting cap at regular intervals and after every change in ingredients, composition or packaging, or as may be requested by the State Fire Marshal.
(5) All electrical switches, controls, motors, and lights, if located in the mixing room, shall conform to the requirements of Class II, Division 2 of the National Electrical Code, otherwise, they shall be located outside the mixing room. The frame of the mixer and all other equipment that may be used shall be electrically bonded and be provided with a continuous path to the ground.
(6) Washdown facilities shall be provided. Floors shall be constructed so as to eliminate open floor drains and piping into which molten materials could flow and be confined in case of fire. The floors and equipment of the mixing and packaging room shall be washed down frequently to prevent accumulation of oxidizers or fuels and other sensitizers. The entire mixing and packaging plant shall be washed down periodically to prevent excessive accumulation of dust.
(7) Smoking or open flames shall not be permitted in or within 50 feet of any building or facility used for the mixing of blasting agents.
(8) Empty oxidizer bags shall be disposed of daily in a safe manner.
(9) Not more than one day's production of blasting agents shall be permitted in or near the mixing and packaging plant or area. Larger quantities shall be stored in separate warehouses or magazines in accordance with rule 69A-2.006, F.A.C.
Rulemaking Authority 552.13 FS. Law Implemented 552.13 FS.
New 6-25-66, Repromulgated 12-24-74, Formerly 4A-2.05, 4A-2.005.