Current through Reg. 50, No. 187; September 24, 2024
(1) New
construction and additions:
(a) This Rule
applies to all of the following:
1. New
facilities constructed for the use of a state agency.
2. Additions to existing state-owned
facilities.
3. Renovations to
existing state-owned facilities shall be allowed to comply with subsection
60D-4.004(1),
F.A.C., when the agency determines that the scope of the proposed renovation
addresses enough energy-consuming equipment and architectural elements to
comply with the whole-building energy performance requirements as described in
this Rule. Otherwise, subsection
60D-4.004(2), (3) or
(4), F.A.C., shall apply.
(b) Alternative designs:
1. At least three alternative designs shall
be developed for the agency's consideration.
2. Each alternative design shall be modeled
with a computer-based simulation program to simulate total energy usage for the
entire building or addition.
3.
Each alternative design shall be modeled with the same computer-based
simulation program.
4. The
computer-based simulation program shall comply with Rule
60D-4.005, F.A.C.
5. The computer-based simulation shall
include HVAC heat load calculations and equipment sizing. The HVAC heat load
calculations shall include all internal building heat loads.
6. Specific energy performance requirements:
a. Maximum allowable energy consumption: The
maximum allowable annual energy consumption for alternative designs shall be
based on the minimum energy performance requirement of the sustainable building
rating adopted by the agency in accordance with Section
255.257(4)(a),
F.S.
b. For new construction and
additions:
(I) The first alternative design
shall demonstrate equal or less energy consumption than the maximum allowable
energy consumption described in sub-subparagraph (1)(b)6.a. of this
section.
(II) The second
alternative design shall demonstrate a percentage reduction in energy
consumption of 10 percent, or more, when compared to the maximum allowable
energy consumption as described in in sub-subparagraph (1)(b)6.a. of this
section.
(III) The third
alternative design shall demonstrate a percentage reduction in energy
consumption of 20 percent, or more, when compared to the maximum allowable
energy consumption as described in in sub-subparagraph (1)(b)6.a. of this
section.
(IV) Additional
alternative designs, if developed, shall demonstrate equal or less energy
consumption than the maximum allowable energy consumption described in in
sub-subparagraph (1)(b)6.a. of this section.
c. For renovations pursuant to subparagraph
60D-4.004(1)(a)
3., F.A.C.:
(I) Two alternative designs shall
demonstrate equal or less energy consumption than the maximum allowable energy
consumption described in in sub-subparagraph (1)(b)6.a. of this
section.
(II) The third alternative
design shall demonstrate a percentage reduction in energy consumption of 10
percent, or more, when compared to the maximum allowable energy consumption as
described in in sub-subparagraph (1)(b)6.a. of this section.
(III) Additional alternative designs, if
developed, shall demonstrate equal or less energy consumption than the maximum
allowable energy consumption described in in sub-subparagraph (1)(b)6.a. of
this section.
d. The
percentage reduction (PR) shall be calculated as follows:
PR = 100 x (required consumption - proposed consumption) /
required consumption
(c) Selection of preferred design:
1. The selection of the preferred alternative
design shall be made by the agency only after a life-cycle cost analysis is
performed in compliance with Rule
60D-4.006, F.A.C.
2. For new facilities and additions,
construction shall proceed only after the life-cycle cost analysis has been
evaluated by the department for technical correctness and completeness,
pursuant to Section 255.254(1),
F.S.
(d) Preparation
requirements: The preparation of alternative designs and the computer-based
energy simulation described in subsection
60D-4.004(1),
F.A.C., shall be performed by an architect or engineer licensed in
Florida.
(2) Major
equipment-related projects:
(a) This Rule
applies to renovations in existing state-owned facilities whenever any one of
the following items of energy-consuming equipment is installed new or replaced:
1. Chillers with a total cooling capacity of
25 tons (300, 000 BTUH) or greater.
2. Boilers with a total input heating
capacity of 300, 000 BTUH (88 kW) or greater.
3. Unitary HVAC equipment (single and
multiple units) within a single building where the total cooling or heating
capacity being installed in the project is 25 tons (300, 000 BTUH) or greater.
Unitary HVAC equipment as defined here shall include:
a. Self-contained air-conditioners and heat
pumps;
b. Complete split system
air-conditioners and heat pumps, which shall be defined here as the both the
condenser and evaporator sections of the system;
c. Fuel-burning furnaces;
d. Electric heaters.
4. Service water heaters (single and multiple
units) within a single building where the total input heating capacity being
installed in the project is 300, 000 BTUH (88 kW) or greater.
5. Lighting fixtures within a single building
where the total lighting capacity being installed in the project is 30 kW or
greater.
(b) This rule
excludes "guaranteed energy, water, and wastewater performance savings
projects" as defined in Section
489.145, F.S.
(c) Exception: New and replacement
energy-consuming equipment intended to serve as back-up equipment that only
operates if primary equipment fails may be omitted from the computer-based
simulation and life-cycle cost analysis requirements of this rule at the
agency's discretion. Such back-up equipment shall be considered to have a
negligible impact to the agency's overall energy consumption due to infrequent
operation. However, the computer-based simulation and life-cycle cost analysis
requirements of this rule shall be applicable to all other aspects of the same
renovation project per paragraph
60D-4.004(2)(a),
F.A.C. This exception does not apply to supplemental equipment, which shall be
defined here as energy-consuming equipment that is intended to operate
regularly for the purposes of meeting peak load requirements.
(d) Alternative designs:
1. At least three alternative designs shall
be developed for the agency's consideration.
2. Each alternative design shall be modeled
with a computer-based simulation program to simulate the total energy usage of
all energy-consuming equipment being installed new or replaced within the
project.
Exception: For projects where lighting fixtures, service
water heaters, or a combination of both are the only energy-consuming equipment
being installed new or replaced, the energy usage of the alternative designs
shall be considered unrelated to the effects of weather and therefore may be
developed manually without a computer-based simulation at the agency's
discretion.
3. The
computer-based simulation shall include HVAC heat load calculations and
equipment sizing for projects that include new or replacement HVAC equipment.
The HVAC heat load calculations shall include all internal building heat loads
for the areas affected by the renovation.
4. The computer-based simulation program
shall comply with Rule
60D-4.005, F.A.C.
5. Specific energy performance requirements:
a. Each alternative design shall meet or
exceed the minimum energy performance requirements of the sustainable building
rating adopted by the agency in accordance with Section
255.257(4)(a),
F.S.
b. Each alternative design
shall demonstrate different energy consumption.
6. Equipment type requirements:
a. HVAC equipment:
(I) Water-cooled equipment replacements: When
the existing HVAC equipment being replaced utilizes cooling towers or ground
water for heat rejection purposes, at least one alternative design shall
incorporate water-cooled equipment, unless there exist conditions outside of
the agency's control as listed in the exceptions below.
(A) Exceptions:
i. The existing supply or return well has
failed and is not repairable.
ii.
The permit application for groundwater consumption has been denied by the
authority having jurisdiction or will not be renewed.
iii. The amount of groundwater available from
the well system or permitted by the authority having jurisdiction is
insufficient for proper or reliable HVAC equipment operation.
iv. New water-cooled or related equipment
will not fit in the available space.
v. The space available to install new
water-cooled or related equipment does not comply with the clearance
recommendations or requirements of the equipment manufacturer.
vi. Applicable codes and ordinances that
prohibit the installation of such equipment.
(II) Centrifugal chiller replacements: When
the HVAC equipment being replaced includes one or more centrifugal type
chillers, at least one alternative design shall incorporate one or more
centrifugal type chillers, unless there exist conditions outside of the
agency's control as listed in the exceptions below.
(A) Exceptions:
i. A new centrifugal type chiller will not
fit in the available space.
ii. The
space available to install a new centrifugal type chiller or related equipment
does not comply with the clearance recommendations or requirements of the
equipment manufacturer.
iii.
Applicable codes and ordinances that prohibit the installation of such
equipment.
b. Lighting equipment:
(I) For office areas:
(A) T-5 fluorescent lighting shall be
included in at least one alternative design when lighting fixtures are to be
installed new or replaced.
(B) Task
lighting shall be included in at least one alternative design when lighting
fixtures are to be installed new or replaced.
(II) Lamp and ballast replacements for
existing lighting fixtures shall be considered an acceptable alternative
design.
c. Service water
heating equipment:
(I) Water heater
replacements: When the equipment being replaced utilizes natural gas, at least
one alternative design shall incorporate natural gas.
(II) Low flow plumbing fixtures shall be
considered an acceptable alternative design for service water
heaters.
(e) Selection of preferred design: The
selection of the preferred alternative design shall be made by the agency only
after a life-cycle cost analysis is performed in compliance with Rule
60D-4.006, F.A.C.
(f) Preparation requirements: The preparation
of alternative designs and the computer-based energy simulation described in
subsection 60D-4.004(2),
F.A.C., shall be performed by an architect or engineer licensed in
Florida.
(3) Minor
equipment-related projects:
(a) This Rule
applies to renovations in existing state-owned facilities whenever any of the
following items of energy-consuming equipment are installed new or replaced:
1. Chillers with a total cooling capacity of
less than 25 tons (300, 000 BTUH).
2. Boilers with a total input heating
capacity of less than 300, 000 BTUH (90 kW).
3. Unitary HVAC equipment (single and
multiple units) within a single building where the total cooling or heating
capacity being installed in the project is less than 25 tons (300, 000 BTUH).
Unitary HVAC equipment as defined here shall include:
a. Self-contained air-conditioners and heat
pumps;
b. Complete split system
air-conditioners and heat pumps, which shall be defined here as both the
condenser and evaporator sections of the system;
c. Fuel-burning furnaces;
d. Electric heaters.
4. Service water heaters (single and multiple
units) within a single building where the total input heating capacity being
installed in the project is less than 300, 000 BTUH (88 kW).
5. Lighting fixtures within a single building
where the total lighting capacity being installed in the project is less than
30 kW.
(b) This rule
excludes "guaranteed energy, water, and wastewater performance savings
projects" as defined in Section
489.145, F.S.
(c) Exception: The agency shall be permitted
to strive for higher energy performance results at its discretion by requiring
compliance with subsection
60D-4.004(2),
F.A.C., thereby requiring a computer-based simulation and life-cycle cost
analysis.
(d) Alternative designs:
1. There is no minimum number of alternative
designs required.
2. Specific
energy performance requirement: Each alternative design shall meet or exceed
the minimum energy performance requirements of the sustainable building rating
adopted by the agency in accordance with Section
255.257(4)(a),
F.S.
(4)
Guaranteed energy, water, and wastewater performance savings projects:
(a) Applies to all "guaranteed energy, water,
and wastewater performance savings projects" as defined in Section
489.145, F.S.
(b) A baseline energy model shall be
developed with a computer-based simulation program to simulate the total
existing energy usage for the building(s) included in the analysis.
(c) Alternative designs shall be developed
with a computer-based simulation program to simulate total energy usage for the
building(s) after the implementation of the proposed energy conservation
measures.
(d) The baseline energy
model and the alternative designs shall be developed with the same
computer-based simulation program.
(e) The computer-based simulation program
shall comply with Rule
60D-4.005, F.A.C.
(f) The computer-based simulation shall
include HVAC heat load calculations and equipment sizing. The HVAC heat load
calculations shall include all internal building heat loads.
(g) Alternative designs:
1. The agency shall specify the number of
alternative designs. One alternative design shall be considered
acceptable.
2. Specific energy
performance requirement: Each alternative design shall meet or exceed the
minimum energy performance requirements of the sustainable building rating
adopted by the agency in accordance with Section
255.257(4)(a),
F.S.
(h) Selection of
preferred design:
1. The selection of the
preferred design or scope of work shall be made by the agency only after an
investment grade energy audit as defined in Section
489.145(3)(f),
F.S., is reviewed by the department in accordance with Sections
489.145(4)(c)
and 489.145(6),
F.S.
2. Life-cycle cost analysis:
a. The investment grade energy audit required
in Section 489.145(6),
F.S., shall include a life-cycle cost analysis for each alternative design and
the baseline energy model that complies with subsection
60D-4.004(6),
F.A.C.
b. The life-cycle cost
analysis for the baseline energy model shall incorporate all
reasonably-expected costs based on the computer-based simulation throughout the
analysis period assuming no energy conservation measures are
employed.
c. The results of the
life-cycle cost analysis as described in Rule
60D-4.006, F.A.C., shall not
replace any part of the investment grade energy audit required in Section
489.145(6),
F.S., or be used as the basis of guaranteed cost savings, but shall be based on
the information contained within the investment grade energy audit in
accordance with Rule 60D-4.006, F.A.C. The life-cycle
cost analysis as described in Rule
60D-4.006, F.A.C., shall be used
by the agency and the department in conjunction with the investment grade
energy audit to assist in the evaluation of the project's life-cycle costs
pursuant to Sections 489.145(4)(c)
and 255.255(1),
F.S.
(i)
Preparation requirement: The preparation of alternative designs and the
computer-based energy simulation described in subsection
60D-4.004(4),
F.A.C., shall be performed by the "guaranteed energy, water, and wastewater
performance savings contractor" as defined in Section
489.145,
F.S.
Rulemaking Authority
255.255 FS., Section 61, Chapter
210-176, Laws of Florida. Law Implemented
255.255,
255.256 FS.
New 5-26-76, Formerly 13D-10.04, 13D-10.004, Amended
3-17-10.