Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
706 - Specific Occupancy Requirements
Chapter 7 - Haunted Houses
Section 706-7-4.0 - Protection

Universal Citation: 1 DE Admin Code 706-7-4.0

Current through Register Vol. 28, No. 3, September 1, 2024

4.1 Fire Extinguishers: At least one portable multi-purpose fire extinguisher, with a minimal rating of 2A:10BC, shall be provided and properly mounted in each room able to be occupied by the public and at each exit and entrance.

4.2 Smoke Alarms: Smoke alarms shall be located in all hallways, corridors, and rooms on all levels.

4.3 Public Address System: A public address system shall be provided throughout in order to notify occupants to evacuate.

4.4 Fire Company Stand-By

4.4.1 Arrangements shall be made with the local fire company to have a stand-by crew provided on location during all hours that the haunted house is operating and/or open to the public.

EXCEPTION 1 FIRE COMPANY STAND-BY SHALL NOT BE REQUIRED IF BUILDING IS FULLY SPRINKLERED.

4.4.2 The Stand-By detail shall consist of at least one standard pumper with its water supply being a minimum 1000 gallon, a crew of at least four, and two-way radio communication with the dispatch center.

Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.