Chapter 7 - Haunted Houses
Section 706-7-2.0 - Construction

Universal Citation: 1 DE Admin Code 706-7-2.0

Current through Register Vol. 28, No. 3, September 1, 2024

2.1 Haunted Houses shall only be allowed to operate on the level of exit discharge as well as one story above the level of discharge.

2.2 Occupants shall be prohibited from areas not on the level of exit discharge or the story above it. Provisions shall be made to physically bar occupants from entering areas not on the level of exit discharge and areas not open to the public.

2.3 Haunted houses shall not be allowed in windowless buildings.

2.4 Walls and windows may use 1/4-inch plywood as covering (minimum standard). Walls are to consist of 3/8 inch plywood and/or drywall.

2.5 Foam rubber, urethane foam, or any other type of expanded combustible material known to burn readily shall not be permitted in the building. Black plastic (fire resistive only) or fire treated cloth may be used on walls.

Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.