5.1 General.
5.1.1 Storage or handling of tires
shall not be located so as to seriously expose adjoining or adjacent properties
in the event of a fire.
5.1.2
Weeds, grass, and similar vegetation shall be eliminated throughout the entire
yard. Combustibles shall be removed as they accumulate.
5.1.3 Smoking shall be prohibited within the
tire storage area. Other types of potential ignition sources, such as cutting
and welding, heating devices, and open fires, shall be prohibited.
5.1.4 Suitable safeguards shall be provided
to minimize the sparks from such equipment as refuse burners, boiler stacks,
and vehicle exhaust.
5.2 Security Of Storage Yards.
5.2.1 A security
fence shall be placed so as to completely enclose the yard containing outdoor
tire storage. A minimum height of six feet of chain link, plus two strands of
barbed wire shall be provided.
5.2.2 Access gate(s) shall be installed in
accordance with the State Fire Marshal.
5.2.3 Twenty-four (24) hour per day manned
security shall be provided to limit access and to provide for communications to
the appropriate fire dispatch center.
EXCEPTION NO. 1: SITES STORING LESS THAN 10,000 UNITS.
EXCEPTION NO. 2: WHEN THE STATE FIRE MARSHAL DETERMINES THAT IT IS NOT NECESSARY FOR SITES STORING MORE THAN 10,000 UNITS.
5.2.4 Security
lighting shall be provided with constant illumination of the yard during hours
of darkness.
EXCEPTION NO. 1: SITES STORING LESS THAN 10,000 UNITS.
EXCEPTION NO. 2: WHEN THE STATE FIRE MARSHAL DETERMINES THAT IT IS NOT NECESSARY FOR SITES STORING MORE THAN 10,000 UNITS.
5.3 Storage Of Tires.
5.3.1 Tires shall be placed
on solid, level ground.
5.3.2 The
method of stacking shall be solid piles in an orderly manner.
5.3.3 The yard shall be maintained free of
other combustible materials and debris.
5.3.4 A minimum of a 50 foot wide clear zone
shall be established between the inside perimeter of the security fence and
tire piles.
5.3.5 Earthen or other
suitable barriers of a minimum height of 30 inches shall be provided to contain
the potential liquid products of combustion resulting from a fire to the pile
of origin.
Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.