Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
706 - Specific Occupancy Requirements
Chapter 5 - Outdoor Tire Storage and Disposal Sites
Section 706-5-4.0 - Exposure Protection
Universal Citation: 1 DE Admin Code 706-5-4.0
Current through Register Vol. 28, No. 3, September 1, 2024
4.1 For 10,000 Units Or Less.
4.1.1 Maximum pile
height shall be 14 feet.
4.1.2 Pile
width and length shall not exceed 25 feet by 100 feet.
4.1.3 Aisle width between piles shall be a
minimum of 24 feet.
4.1.4 The
minimum distance between piles and buildings shall be 25
feet.
4.2 For More Than 10,000 Units.
4.2.1 Maximum pile height shall
be 20 feet.
4.2.2 Pile width and
length shall not exceed 50 feet by 100 feet.
4.2.3 Aisle width between piles shall be a
minimum of 24 feet.
4.2.4 The
minimum distance between piles and important buildings shall be 200
feet.
4.2.5 If the minimum distance
required in § 4.2.4 cannot be provided, a Two Hour Rated Fire Wall (Class
"B" Fire Barrier) shall be provided in accordance with Regulation 702, Chapter
2. This Two Hour Rated Wall shall be equal to or exceed the height of the
pile(s).
Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.