Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
706 - Specific Occupancy Requirements
Chapter 2 - Bed and Breakfasts
Section 706-2-2.0 - General Requirements
Current through Register Vol. 28, No. 3, September 1, 2024
2.1 Not more than the second floor of the structure will be utilized for the rented rooms.
2.2 Each rented room shall have at least one primary means of escape and one secondary means of escape in accordance with the Chapter of the Life Safety Code, NFPA 101 that addresses One and Two-Family Dwellings, as adopted and/or modified by these Regulations.
2.3 A comprehensive smoke detection system is installed throughout the structure, and in accordance with the Chapter of the Life Safety Code, NFPA 101 that addresses One and Two-Family Dwellings and the Chapter of the Life Safety Code, NFPA 101 that addresses Building Services and Fire Protection Equipment, as adopted and/or modified by these Regulations.
2.4 Unvented fuel-fired heating equipment shall be prohibited in bathrooms and sleeping areas. Exception: In all other areas, gas space heaters installed in compliance with NFPA 54, National Fuel Gas Code, as adopted and/or modified by these Regulations.
Note: This requirement also appears in Regulation 701 and reappears in this specific occupancy Chapter for clarification. |