Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
705 - General Fire Safety
Chapter 5 - Access for Emergency Personnel and Apparatus
Section 705-5-4.0 - Emergency Services Access to Buildings That Require Fire Lanes
Current through Register Vol. 28, No. 3, September 1, 2024
4.1 This section applies to all buildings:
4.2 Fire Lane Access and Perimeter Access shall be in accordance with Table 5-2.
Note: See Figure 5-8 - Fire Lane and Perimeter Access - Without Fire Suppression |
4.3 The State Fire Marshal may consider other design criteria for existing properties in a traditional urban setting on an individual basis, based upon the nature and degree of hazard associated with the building and/or characteristics of the site.
4.4 Fire Lanes shall be provided and designed in accordance with Section 6.0 of this chapter and marked in accordance with Section 7.0 of this chapter.
4.5 Perimeter Access minimum width shall be 15 feet measured from the face of the building at grade with a maximum slope of ten percent (10%). Plantings and utility services (includes condenser units, transformers, etc.) shall be permitted within the perimeter access, provided they do not interfere with the emergency services fire ground operations.
Note: See Figure 5-9 - Fire Lane and Perimeter Access with Fire Suppression |
Accessibility Table
Table 5-2
Percent of Fire Lanes | Percent of Perimeter Access | |||||
Number of Stories | 1-2 | 3-4 | > 4 | 1-2 | 3-4 | > 4 |
Height | up to 25' | >25 to 50' | > 50' | up to 25' | >25 to 50' | > 50' |
OCCUPANCY1 | ||||||
Assembly | 50 | 50 | 50 | N/A | N/A | 100 |
Educational2 | 50 | 75 | 75 | N/A | N/A | 100 |
Day Care Center | 25 | 50 | 75 | 50 | 75 | 100 |
Hospital | 50 | 75 | 75 | 100 | 100 | 100 |
Nursing Home | 25 | 50 | 75 | 75 | 75 | 100 |
Ambulatory Health Care | 25 | 25 | 50 | N/A | 50 | 75 |
Detention & Correction | TBDFM | TBDFM | TBDFM | TBDFM | TBDFM | TBDFM |
Residential | 25 | 35 | 75 | 50 | 75 | 100 |
Mercantile | 25 | 50 | 50 | 50 | 75 | 75 |
Business | 25 | 25 | 50 | N/A | 50 | 75 |
Industrial | 25 | TBDFM | TBDFM | 50 | TBDFM | TBDFM |
Storage | 25 | TBDFM | TBDFM | 50 | TBDFM | TBDFM |
TBDFM = To Be Determine in consultation with the Office of the State Fire Marshal.
1. For Mixed Use occupancies, accessibility shall be based on the floor with the individual occupancy requiring the greatest accessibility coverage.
2. Educational shall include educational buildings with mixed uses and shall not be considered as mixed use
Note: For the purposes of this Regulation and application of the Accessibility Table, the fire lane portion was based upon a 100 foot Aerial reach and the width of aerial stabilizers. The Perimeter Access portion was based upon standard fire ground operations. |