Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
705 - General Fire Safety
Chapter 5 - Access for Emergency Personnel and Apparatus
Section 705-5-3.0 - Emergency Services Access to Buildings
Current through Register Vol. 28, No. 3, September 1, 2024
3.1 This section shall apply to buildings that do not require fire lanes but still require emergency services accessibility.
3.2 Building Access shall be in accordance with Table 5-1.
Table 5-1
Accessibility Table
TBDFM = To Be Determined in consultation with the Office of the State Fire Marshal.
3.3 The State Fire Marshal may consider other design criteria for existing properties in a traditional urban setting on an individual basis, based upon the nature and degree of hazard associated with the building and/or characteristics of the site.
3.4 Streets and Access Roadways shall be permitted to be utilized to achieve the required Building Access.
Note: See Figure 5-6 - Building Access - With No Fire Lane
3.5 Perimeter Access minimum width shall be 10 feet for one-story buildings and 15 feet for buildings of two or more stories, measured from the face of the building at grade with a maximum slope of ten percent (10%). Plantings and utility services (includes condenser units, transformers, furniture, etc.) shall be permitted within the perimeter access, and shall not interfere with emergency services fire ground operations.
3.6 Access to fire protection features shall meet the requirements of Chapter 6.
Note: See Figure 5-7 - Perimeter Access - With No Fire Lane