Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
703 - Installation, Operation, Maintenance, Testing and Sales of Signaling Systems, Fire Protection Systems and Fire Extinguishers
Chapter 1 - Operation, Maintenance, and Testing of Fire Protection Systems
Section 703-1-4.0 - Periodic Inspections, Testing, And Maintenance Service
Universal Citation: 1 DE Admin Code 703-1-4.0
Current through Register Vol. 28, No. 3, September 1, 2024
4.1 General.
4.1.1 Periodic inspections, testing, and
maintenance of fire alarm signaling, fire suppression, and any other fire
protection systems, devices, and equipment shall be conducted in accordance
with the National Fire Protection Association's National Fire Codes and
Standards, as adopted and/or modified by these Regulations. The required
inspection, testing, and maintenance service shall be conducted by a licensed
company or by an owners representative at the intervals established by the
National Fire Protection Association's National Fire Codes and Standards, as
adopted and/or modified by these Regulations.
4.1.2 Before testing any suppression system,
standpipe, or fire alarm system which is connected to a central station or
connected directly to a fire dispatch center, or the fire or police department,
notification shall be given to the central station, fire dispatch center, fire
department or police department before initiation of the tests.
4.1.3 It shall be the responsibility of the
owner of the protected property to see that the required periodic inspections,
testing, and maintenance of the system are conducted, as well as having the
system serviced whenever an unexplained activation of the system occurs or if
the system is found to be inoperative.
4.1.4 Annual Inspection, Testing, and
Maintenance Service. Annual inspection, testing, and maintenance is required
for all fire alarm signaling, fire suppression, and any other fire protection
systems, devices, and equipment installed within the State of Delaware. This
annual inspection, testing, and maintenance service shall be completed by a
company licensed in accordance with Regulation 703, Chapters 2, 4, 5, 6, and/or
7. Upon completion of this annual inspection, testing, and maintenance service,
the licensed company shall submit an Annual Certificate of Inspection along
with the appropriate fees as listed in these Regulations, in accordance with
§ 4.1.5 of this Chapter.
4.1.5
Certificate of Inspection. A separate Certificate of Inspection is required to
be forwarded to the State Fire Marshal on an annual basis and on the prescribed
form for all such fire alarm, fire suppression, and other fire protection
systems that are required to be inspected, tested, and/or maintained by these
Regulations. The Annual Certificate of Inspection must be submitted to the
Office of the State Fire Marshal within 30 days of the completion of the
required annual testing, inspection, or maintenance by a company licensed in
accordance with Chapters 4, 5, 6, and/or 7 of this Regulation. A Certificate of
Inspection shall also be completed after each periodic inspection, test, or
maintenance, and shall be maintained on site as part of the permanent systems
record.
4.1.6 Fire Protection Major
Deficiencies.
4.1.6.1 Where a fire protection
system major deficiency is found, it shall be reported to the Office of the
State Fire Marshal within one business day on a form prescribed by the Office
of the State Fire Marshal.
4.1.6.2
When a fire protection system major deficiency is repaired, it shall be
reported to the Office of the State Fire Marshal within one business day on a
form prescribed by the Office of the State Fire Marshal.
4.1.7 The failure of the licensed company to
comply with the provisions of this section, shall constitute a violation of the
Delaware State Fire Prevention Regulations.
4.2 Standpipes.
4.2.1 All standpipe fire lines in all
buildings and structures shall be tested at least every five years. In
buildings and structures having floors used for human occupancy located more
than 50 feet above the lowest level of fire department vehicle access, tests
shall be made at intervals of not more than two years. Wet and dry pipe systems
shall meet the flow demands required at the time of installation or as required
by § 5.1.2 of this Chapter. At the time of the test all control valves,
including those inside hose cabinets, shall be operated and then reset in their
proper position to insure the workability of these valves. Wet and dry systems
unable to meet the flow requirements at the time of installation or as required
by § 5.1.3 of this Chapter shall be required to install automatic fire
pumps or tanks if deemed necessary by the State Fire Marshal for the occupancy
of the building.
4.3 Sprinkler System Tests.
4.3.1 All sprinkler
systems shall have the proper inspections, tests, and maintenance performed at
the prescribed intervals in accordance with the National Fire Protection
Association's National Fire Codes and Standards as adopted and/or modified by
these Regulations.
4.4 Fire Pumps.
4.4.1 All fire pumps shall have
the proper inspections, tests, and maintenance performed at the prescribed
intervals in accordance with the National Fire Protection Association's
National Fire Codes and Standards as adopted and/or modified by these
Regulations. Where the water supply is from a public service main, pump
operation and testing shall not draw the residual suction pressure at the pump
below 10 PSI.
Exception: This requirement may be waived where the water supply is consistently above the sprinkler system demand.
4.5 Fire Suppression Systems for Cooking Operations.
4.5.1 Every fire suppression
system for cooking operations shall be inspected at least every six months and
whenever the system activated or found inoperative. Inspections shall be made
only by companies or individuals licensed under the provisions of these
Regulations. All actuation components, including remote manual pull stations,
mechanical or electrical devices, detectors, actuators, etc., shall be checked
for proper operation during inspection. All fusible links and fusible link
sprinkler heads shall be replaced annually. Manual stations shall be sealed and
safety pinned or latched. An inspection tag shall be located at the manual pull
station indicating the date of the last inspection and the name and license
number of the company who performed the work as well as the signature of the
responsible party.
4.5.2 A
Certificate of Inspection shall be forwarded to the Office of the State Fire
Marshal on an annual basis, or whenever any system is placed back into service
after being discharged. This Certificate of Inspection must be submitted by a
company licensed in accordance with Chapters 4, 5, 6, and/or 7 of this
Regulation. A Certificate of Inspection shall also be completed after each
periodic inspection, test, or maintenance and shall be maintained on site as
part of the permanent systems record. Certificates of Inspection shall be
submitted in such form as the State Fire Marshal may
prescribe.
4.6 Fire Alarm Systems.
4.6.1 All fire alarm signaling
systems shall have the proper inspection, testing and maintenance service
performed at the prescribed intervals in accordance with the National Fire
Protection Association's National Fire Codes and Standards as adopted and/or
modified by these Regulations.
4.6.2 In Non-Transient Tenant Occupied
Households, such as apartments, rental condominiums, and one- and two-family
rental property, the landlord shall provide the tenant with information
describing the operation, method, and frequency of testing and proper
maintenance of household fire warning equipment. The tenant shall test the
household fire warning equipment in accordance with the National Fire Code,
NFPA 72, as adopted and/or modified by these Regulations.
4.6.3 In Transient Tenant Occupied Households
such as apartments, hotels, motels, dormitories, residential board and care and
boarding houses. The landlord shall be required to have a licensed fire alarm
signaling system company test the household fire warning equipment in
accordance with the National Fire Code, NFPA 72, as adopted and/or modified by
these Regulations. A written record of the tests and inspections shall be
completed in accordance with § 4.8 of this Chapter.
4.7 Fire Safety Devices.
4.7.1 Special fire safety devices including
automatic smoke removal and control equipment, emergency generators and any
other special fire safety equipment shall be tested annually by the owner or an
authorized representative and the results of such tests shall be logged in a
journal kept available for inspection in accordance with procedures approved by
the State Fire Marshal.
4.8 Test Records; Tagging.
4.8.1 Written Record. A log or other complete
written record of all tests and inspections required under this Chapter shall
be maintained on the premises by the owner or occupant in charge of said
premises. The written record shall document the inspection or testing of each
individual system component required to be tested or inspected. The written
record must reference each component by use of an identification
number.
4.8.2 Identification
Number. All system components required to be tested or inspected under this
Chapter shall have a unique identification number assigned. The assigned number
shall be displayed on the device in such a way so that each component shall be
easily and readily identified in the installed state. If it is impossible to
identify the device by the display of a tag, the State Fire Marshal may approve
an alternative method.
4.8.3
Certificate of Inspection. A separate Certificate of Inspection is required to
be forwarded to the Office of the State Fire Marshal, on an annual basis, and
on the prescribed form, for all such fire alarm, fire suppression, or other
fire protection systems that are required to be serviced, tested, or maintained
by these Regulations. This Certificate of Inspection must be submitted by a
company licensed in accordance with Regulation 703, Chapters 4, 5, 6, and/or 7.
A Certificate of Inspection shall also be completed after each periodic
service, test, or inspection and shall be maintained on site as part of the
permanent systems record.
4.8.4
Inspection and Maintenance Tag. An inspection and maintenance tag shall be
affixed to the face of the system's main control after each completed
inspection or test. The inspection and maintenance tag shall indicate the
following:
4.8.4.1 Location or identification
of system;
4.8.4.2 Name, address,
telephone number, and license number of the fire alarm signaling/ suppression
systems company;
4.8.4.3 Date of
inspection or maintenance visit;
4.8.4.4 Name and certificate number of
employee in responsible charge of inspection or maintenance visit;
4.8.4.5 Type of system inspected or
maintained. (Types of systems shall be per the Certificate of
Installation.)
4.9 Dry Hydrants.
4.9.1 Where dry hydrants are installed in any
subdivision, development, complex, or community that has a common maintenance
agreement to which the landowners either subscribe to or pay a fee, for any
maintenance, repair or other improvements, it shall be the responsibility of
the landowners to maintain and test all such dry hydrants as may be installed
according to the specifications set out in this section.
4.9.2 The provisions of § 4.9.1 of this
Chapter shall apply to all dry hydrants that may be installed on any private
property, be it residential, commercial, or industrial, and the owner of such
properties or occupancies shall be responsible for the periodic inspections,
maintenance, and testing of the dry hydrants.
4.9.3 All dry hydrants will be reverse
flushed on an annual basis.
4.9.4
All dry hydrants shall be inspected and operated on an annual basis with
particular attention paid to the general condition of the dry hydrant to
include:
4.9.4.1 Caps present and free
turning;
4.9.4.2 Threads in good
condition;
4.9.4.3 Hydrant operates
properly;
4.9.4.4 Hydrant drains
properly;
4.9.4.5 All piping is in
good condition with no visible breaks or cracks;
4.9.4.6 Fire department connection facing in
the right direction;
4.9.4.7 There
are no physical obstructions; and
4.9.4.8 Fire department access is not
blocked, impeded, nor hindered.
4.9.5 A copy of the annual inspection and
maintenance report shall be submitted to the local Fire Chief.
4.9.6 The owner will have all necessary
repairs made or deficiencies corrected within 30 days of any periodic
inspection, maintenance, or testing that indicates such action is
needed.
4.9.7 Records of
inspections and corrective actions for noted deficiencies shall be maintained
by the owner at their main office for a period of three (3)
years.
Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.