Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
702 - Fire Protection in Building Construction
Chapter 6 - Standard for Fire Flow for Fire Protection
Section 702-6-5.0 - Fire Hydrants
Universal Citation: 1 DE Admin Code 702-6-5.0
Current through Register Vol. 28, No. 3, September 1, 2024
5.1 Spacing and Location.
5.1.1 Hydrant spacing as shown
in the Fire Flow Tables shall be used as a general rule. Hydrants shall be
located at the direction of the State Fire Marshal so as to minimize friction
in fire hose. All hydrant spacing shall be located along available roads or at
the direction of the State Fire Marshal. This measurement shall be calculated
by way of accessible thoroughfare(s) from the building to be protected to the
hydrant and may not necessarily be a radius.
5.1.2 Hydrants shall be provided in such a
manner that all fire department connections and/or standpipe connections shall
be within 300' of a hydrant and shall meet the provisions of the applicable
NFPA Regulations as adopted and/or modified by these Regulations. This
measurement shall be calculated by way of accessible thoroughfare(s) from the
proposed fire department connection to the hydrant and may not necessarily be a
radius.
5.1.3 Additional hydrants
shall be provided when the State Fire Marshal deems it necessary based on the
configuration of the site, building(s), exposures, construction, occupancy,
and/or specific hazard(s).
5.2 Number.
5.2.1 The number of hydrants required shall
be based on spacing and location requirements or number of required fire
hydrants, whichever is greater.
5.2.2 Required fire hydrants shall be the
number of fire hydrants required to extract the required flow from the
distribution system in a form and arrangement usable by the fire
department.
5.3 Installation.
5.3.1 Fire hydrants and water
mains shall be installed in accordance with American Water Works Association
Standard and all applicable NFPA codes and standards as adopted and/or modified
by these Regulations.
5.3.2 Fire
hydrants shall be supplied by not less than a six inch diameter main installed
on a looped system or not less than an eight inch diameter main if the system
is not looped or the fire hydrant is installed on a dead end main exceeding 300
feet in length.
5.3.3 Dead end
mains shall not exceed 600 feet in length for main sizes under 10 inches in
diameter.
Exception: Dead end mains exceeding 600 feet may be a minimum of 8 inches in diameter if an engineering analysis, acceptable to the Office of the State Fire Marshal, is submitted by a registered Professional Engineer demonstrating that the minimum flows and duration specified elsewhere in this Regulation are met or exceeded.
5.4 Other.
5.4.1 Fire hydrants installed in accordance
with this requirement shall not be removed or shut down, except when repairs
are necessary, without the permission of the State Fire Marshal.
5.4.2 The water supplier shall call the local
fire dispatch center to report when a fire hydrant is taken out of service for
repairs or maintenance. The supplier is to state the location and the
approximate length of time the hydrant will be out of service. The supplier is
to notify the local fire dispatch center when the hydrant is put back in
service.
Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.