Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
702 - Fire Protection in Building Construction
Chapter 6 - Standard for Fire Flow for Fire Protection
Section 702-6-4.0 - Water Distribution Systems

Universal Citation: 1 DE Admin Code 702-6-4.0

Current through Register Vol. 28, No. 3, September 1, 2024

4.1 Where water is available and a water distribution system is required for stand alone/detached one- and two-family dwelling sites, the infrastructure for fire protection water shall be provided. The infrastructure for fire flow shall consist of properly listed and sized underground mains, stub ups for hydrants, and associated valves. The fire hydrants shall be installed prior to the fire flow requirements taking effect.

4.1.1 For purposes of this Regulation, water for fire protection shall be considered "available" whenever any portion of a proposed project's property or any portion of a proposed subdivision is situated within one thousand (1000) feet of any portion of a water supplier's new or existing infrastructure that includes water supply piping of 4 inches or more in nominal internal diameter. This measurement shall be calculated by way of accessible public thoroughfare(s) from the proposed property or subdivision and may not necessarily be a radius.

4.1.2 In the event the project or subdivision is situated in a geographical area that has been authorized to be provided with water service by a supplier other than the water supplier whose infrastructure is within the specified distance, the State Fire Marshal, on a case by case basis, may re-evaluate the requirements of § 4.1.1.

4.2 The requirements of Fire Flow Table 1, with respect to the Standard on Water Supplies for Suburban and Rural Fire Fighting, NFPA 1142, as adopted and/or modified by these Regulations, may be applied to subdivisions of 25 or less lots of one and two-family detached homes, where central water is provided. However, the requirement for water flow for fire protection shall be required when:

4.2.1 Additional development creates a subdivision in excess of 25 lots of detached one or two-family dwellings or

4.2.2 In the opinion of the State Fire Marshal the probability of additional development will occur in excess of 25 lots of detached one or two-family dwellings then the infrastructure for fire flow capability must be installed to accommodate the fire flow requirements.

4.3 The requirements of Fire Flow Table 2 shall take effect where water is available and be provided under the following circumstances:

4.3.1 For subdivisions of 50 or more lots of detached one and t two-family dwellings the water flow for fire protection shall be provided upon completion of the 50th lot, and prior to the development of the 51st lot.

4.3.2 For subdivisions of 26 through 49 lots of detached one and two-family dwellings the water flow for fire protection shall be provided at the completion of the last lot to be built.

Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.