702 - Fire Protection in Building Construction
Chapter 6 - Standard for Fire Flow for Fire Protection
Section 702-6-4.0 - Water Distribution Systems
Current through Register Vol. 28, No. 3, September 1, 2024
4.1 Where water is available and a water distribution system is required for stand alone/detached one- and two-family dwelling sites, the infrastructure for fire protection water shall be provided. The infrastructure for fire flow shall consist of properly listed and sized underground mains, stub ups for hydrants, and associated valves. The fire hydrants shall be installed prior to the fire flow requirements taking effect.
4.2 The requirements of Fire Flow Table 1, with respect to the Standard on Water Supplies for Suburban and Rural Fire Fighting, NFPA 1142, as adopted and/or modified by these Regulations, may be applied to subdivisions of 25 or less lots of one and two-family detached homes, where central water is provided. However, the requirement for water flow for fire protection shall be required when:
4.3 The requirements of Fire Flow Table 2 shall take effect where water is available and be provided under the following circumstances: