Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
702 - Fire Protection in Building Construction
Chapter 3 - Special Fire Safety Provisions For Physically Handicapped People
Section 702-3-2.0 - Emergency Communication and Fire Alarm Signaling Systems
Universal Citation: 1 DE Admin Code 702-3-2.0
Current through Register Vol. 28, No. 3, September 1, 2024
2.1 Maximum Height.
2.1.1 The maximum mounting height for
emergency communication and alarm system devices shall not be greater than 54
inches from the highest operation control to the floor.
2.2 Visual Alarms Indicating Appliances.
2.2.1 Where fire alarm signaling systems are
required by other sections of these Regulations, both audible and visible alarm
indicating appliances shall be installed.
2.2.2 Visible alarm indicating devices shall
be of the direct viewing strobe type unless in the opinion of the State Fire
Marshal the indirect viewing type are necessary due to the nature of the
occupancy.
2.2.3 All visual
indicating appliances installed shall be strobe lights listed for the
protective signaling purpose for which they are used.
2.2.4 Visual indicating appliances shall be
installed in all areas where required by the State Fire
Marshal.
Disclaimer: These regulations may not be the most recent version. Delaware may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.